2-116 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
N60 78E6 ...Repeated for PMU 3
" 7902 ...Repeated for PMU 4
" 791E ...Repeated for PMU 5
" 793A ...Repeated for PMU 6
Validation Automation (Read/Write Setting)
All 7A00 Validation Automation Setting (16 items) 0 to 4294967295 --- 1 F003 0
Underfrequency (Read/Write Setting) (6 Modules)
D30, D60, F35,
F60, G30, G60,
L30, L90, M60,
N60, T35, T60
7A60 Underfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 7A61 Underfrequency 1 Block 0 to 4294967295 --- 1 F300 0
" 7A63 Underfrequency 1 Min Current 0.1 to 1.25 pu 0.01 F001 10
" 7A64 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 5950
" 7A65 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 2000
" 7A66 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 2000
" 7A67 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 7A68 Underfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 7A69 Underfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7A6A Underfrequency 1 Reserved (5 items) 0 to 1 --- 1 F001 0
" 7A6F ...Repeated for Underfrequency 2
" 7A7E ...Repeated for Underfrequency 3
" 7A8D ...Repeated for Underfrequency 4
" 7A9C ...Repeated for Underfrequency 5
" 7AAB ...Repeated for Underfrequency 6
Thermal Model (Read/Write Grouped Setting)
M60 7AE0 Thermal Model Function 0 to 1 --- 1 F102 0 (Disabled)
" 7AE1 Thermal Model Curve 0 to 5 --- 1 F099 0 (Motor)
" 7AE2 Thermal Model TD Multiplier 0 to 600 --- 0.01 F001 100
" 7AE3 Thermal Model Bias K Factor 0 to 19 --- 1 F001 0
" 7AE4 Thermal Model Time Constant Running 1 to 65000 min 1 F001 15
" 7AE5 Thermal Model Time Constant Stopped 1 to 65000 min 1 F001 30
" 7AE6 Thermal Model Hot Cold Ratio 0.01 to 1 --- 0.01 F001 100
" 7AE7 Thermal Model RTD Bias 0 to 1 --- 1 F102 0 (Disabled)
" 7AE8 Thermal Model RTD Bias Minimum 0 to 250 °C 1 F001 40
" 7AE9 Thermal Model RTD Bias Center 0 to 250 °C 1 F001 130
" 7AEA Thermal Model RTD Bias Maximum 0 to 250 °C 1 F001 155
" 7AEB Thermal Model Start Inhibit Margin 0 to 25 % 1 F001 0
" 7AEC Thermal Model Block 0 to 4294967295 --- 1 F300 0
" 7AEE Thermal Model Events 0 to 1 --- 1 F102 0 (Disabled)
" 7AEF Thermal Model Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7AF0 Thermal Model Curve Effect 0 to 1 --- 1 F096 0 (Cutoff)
" 7AF1 Speed 2 Thermal Model Curve 0 to 5 --- 1 F099 0 (Motor)
" 7AF2 Speed 2 Thermal Model TD Multiplier 0 to 600 --- 0.01 F001 100
" 7AF3 Reserved 0 to 600 --- 0.01 F001 100
" 7AF4 Thermal Model IEC Curve K Factor 1 to 1.5 --- 0.05 F001 110
" 7AF5 Thermal Model IEC Curve Time Constant 0 to 1000 min. 1 F001 45
Products Address Register name Range Units Step Format Default