Voltage Dependent Overload (Read/Write Grouped Setting)
M60 7B00 Voltage Dependent Overload Function 0 to 1 --- 1 F102 0 (Disabled)
" 7B01 Voltage Dependent Overload Minimum
Motor Volts
60 to 99 % 1 F001 80
" 7B02 Voltage Dependent Overload Voltage Loss 0 to 4294967295 --- 1 F300 0
" 7B04 VD Overload Stall Current at Minimum Volts 1.5 to 20 × FLA 0.01 F001 450
" 7B05 VD Overload Safe Stall Time at Minimum
Volts
0.1 to 1000 s 0.1 F001 200
" 7B06 VD Overload Acceleration Intersect at
Minimum Volts
1.5 to 20 × FLA 0.01 F001 400
" 7B07 VD Overload Stall Current at 100% Voltage 1.5 to 20 × FLA 0.01 F001 600
" 7B08 VD Overload Safe Stall Time at 100%
Voltage
0.1 to 1000 s 0.1 F001 100
" 7B09 VD Overload Acceleration Intersect at
100% Voltage
1.5 to 20 × FLA 0.01 F001 500
" 7B0A Speed 2 Voltage Dependent Overload
Function
0 to 1 --- 1 F102 0 (Disabled)
" 7B0B Speed 2 VD Overload Minimum Motor Volts 60 to 99 % 1 F001 80
" 7B0C Speed 2 Voltage Dependent Overload
Voltage Loss
0 to 4294967295 --- 1 F300 0
" 7B0E Speed 2 VD Overload Stall Current at
Minimum Volts
1.5 to 20 × FLA 0.01 F001 450
" 7B0F Speed 2 VD Overload Safe Stall Time at
Minimum Volts
0.1 to 1000 s 0.1 F001 200
" 7B10 Speed 2 VD Acceleration Intersect at
Minimum Volts
1.5 to 20 × FLA 0.01 F001 400
" 7B11 Speed 2 VD Overload Stall Current at 100%
Voltage
1.5 to 20 × FLA 0.01 F001 600
" 7B12 Speed 2 VD Overload Safe Stall Time at
100% Voltage
0.1 to 1000 s 0.1 F001 200
" 7B13 Speed 2 VD Acceleration Intersect at 100%
Voltage
1.5 to 20 × FLA 0.01 F001 500
Motor Acceleration Time (Read/Write Grouped Setting)
M60 7B20 Motor Acceleration Function 0 to 1 --- 1 F102 0 (Disabled)
" 7B21 Motor Acceleration Current 1 to 10 × FLA 0.01 F001 600
" 7B22 Motor Acceleration Time 0.05 to 180 s 0.01 F001 1000
" 7B23 Motor Acceleration Mode 0 to 1 --- 1 F097 0 (Definite
Time)
" 7B24 Motor Acceleration Block 0 to 4294967295 --- 1 F300 0
" 7B26 Motor Acceleration Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7B27 Motor Acceleration Events 0 to 1 --- 1 F102 0 (Disabled)
" 7B28 Speed 2 Motor Acceleration Current 1 to 10 x FLA 0.01 F001 600
" 7B29 Speed 2 Motor Acceleration Time 0.05 to 180 s 0.01 F001 1000
" 7B2A Speed 2 Motor Acceleration Mode 0 to 1 --- 1 F097 0 (Definite
Time)
" 7B2B Speed 2 Motor Acceleration Speed 1-2 0.05 to 180 s 0.01 F001 1000
" 7B2C Speed 2 Motor Acceleration Block 0 to 4294967295 --- 1 F300 0
" 7B2E Reserved (9 items) --- --- --- F001 0
User Programmable Pushbuttons Commands (Read/Write Command) (16 Modules)
All 7B40 User Programmable Pushbutton 1 On
Command
0 to 1 --- 1 F108 0 (Off)
" 7B41 ...Repeated for Pushbutton 2