2-176 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" D43D Synchrocheck 1 V2 Magnitude Correction
Factor
0.1 to 10 --- 0.01 F001 100
" D43E Synchrocheck 1 V2 Angle Shift -180 to 180 --- 1 F002 0
" D43F Synchrocheck 1 Dead Source Select 0 to 5 --- 1 F176 1 (LV1 and
DV2)
" D440 Synchrocheck 1 Dead V1 Maximum
Voltage
0.04 to 1.25 pu 0.01 F001 30
" D441 Synchrocheck 1 Dead V2 Maximum
Voltage
0.04 to 1.25 pu 0.01 F001 30
" D442 Synchrocheck 1 Live V1 Minimum Voltage 0.04 to 1.25 pu 0.01 F001 70
" D443 Synchrocheck 1 Live V2 Minimum Voltage 0.04 to 1.25 pu 0.01 F001 70
" D444 Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" D445 Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" D446 Synchrocheck 1 Block 0 to 4294967295 --- 1 F300 0
" D448 ...Repeated for Synchrocheck 2
" D460 ...Repeated for Synchrocheck 3
" D478 ...Repeated for Synchrocheck 4
C60, D60, L90,
N60, T60
D490 ...Repeated for Synchrocheck 5
" D4A8 ...Repeated for Synchrocheck 6
C60, D60, L90 D4C0 ...Repeated for Synchrocheck 7
" D4D8 ...Repeated for Synchrocheck 8
" D4F0 ...Repeated for Synchrocheck 9
" D508 ...Repeated for Synchrocheck 10
Field Unit Shared Inputs (Read/Write Setting) (16 Modules)
All except B90,
L60
D5C0 Field Shared Input 1 ID 0 to 65535 --- 1 F636 "SI 1"
" D5CA Field Shared Input 1 Unit Origin 1 0 to 8 --- 1 F256 0 (None)
" D5CB Field Shared Input 1 Channel Origin 1 1 to 15 --- 1 F001 1
" D5CC Field Shared Input 1 Events 0 to 1 --- 1 F102 1 (Enabled)
" D5CD ...Repeated for Field Shared Input 2
" D5DA ...Repeated for Field Shared Input 3
" D5E7 ...Repeated for Field Shared Input 4
" D5F4 ...Repeated for Field Shared Input 5
" D601 ...Repeated for Field Shared Input 6
" D60E ...Repeated for Field Shared Input 7
" D61B ...Repeated for Field Shared Input 8
" D628 ...Repeated for Field Shared Input 9
" D635 ...Repeated for Field Shared Input 10
" D642 ...Repeated for Field Shared Input 11
" D64F ...Repeated for Field Shared Input 12
" D65C ...Repeated for Field Shared Input 13
" D669 ...Repeated for Field Shared Input 14
" D676 ...Repeated for Field Shared Input 15
" D683 ...Repeated for Field Shared Input 16
Field Unit Shared Outputs (Read/Write Setting) (16 Modules)
All except B90,
L60
D690 Field Shared Output 1 ID 0 to 65535 --- 1 F636 "SO 1"
" D69A Field Shared Output 1 Operate 0 to 4294967295 --- 1 F300 0