CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-181
2
" EAD4 ...Repeated for PMU 5
" EAE0 ...Repeated for PMU 6
Phasor Measurement Unit Frequency Trigger (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
EAEC PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
" EAED PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
" EAEE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
" EAEF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
" EAF0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
" EAF1 PMU 1 Frequency Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
" EAF7 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
" EAF8 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
C60, N60 EAF9 ...Repeated for PMU 2
N60 EB06 ...Repeated for PMU 3
" EB13 ...Repeated for PMU 4
" EB20 ...Repeated for PMU 5
" EB2D ...Repeated for PMU 6
Phasor Measurement Unit df/dt Trigger (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
EB3A PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
" EB3B PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
" EB3C PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
" EB3D PMU 1 df/dt Trigger Pkp Time 0 to 600 seconds 0.01 F001 10
" EB3E PMU 1 df/dt Trigger Dpo Time 0 to 600 seconds 0.01 F001 100
" EB3F PMU 1 df/dt Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
" EB45 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
" EB46 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
C60, N60 EB47 ...Repeated for PMU 2
N60 EB54 ...Repeated for PMU 3
" EB61 ...Repeated for PMU 4
" EB6E ...Repeated for PMU 5
" EB7B ...Repeated for PMU 6
Phasor Measurement Unit Power Trigger (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
EB88 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
" EB89 PMU 1 Power Trigger Active 0.25 to 3 pu 0.001 F001 1250
" EB8A PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.001 F001 1250
" EB8B PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.001 F001 1250
" EB8C PMU 1 Power Trigger Pkp Time 0 to 600 s 0.01 F001 10
" EB8D PMU 1 Power Trigger Dpo Time 0 to 600 s 0.01 F001 100
" EB8E PMU 1 Power Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
" EB94 PMU 1 Power Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
" EB95 PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
C60, N60 EB96 ...Repeated for PMU 2
N60 EBA4 ...Repeated for PMU 3
" EBB2 ...Repeated for PMU 4
Products Address Register name Range Units Step Format Default