EasyManua.ls Logo

GE b30 - Page 202

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-182 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" EBC0 ...Repeated for PMU 5
" EBCE ...Repeated for PMU 6
Phasor Measurement Unit Calibration (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
EBDC PMU 1 Va Calibration Angle -5 to 5 ° 0.05 F002 0
" EBDD PMU 1 Va Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBDE PMU 1 Vb Calibration Angle -5 to 5 ° 0.05 F002 0
" EBDF PMU 1 Vb Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBE0 PMU 1 Vc Calibration Angle -5 to 5 ° 0.05 F002 0
" EBE1 PMU 1 Vc Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBE2 PMU 1 Vx Calibration Angle -5 to 5 ° 0.05 F002 0
" EBE3 PMU 1 Vx Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBE4 PMU 1 Ia Calibration Angle -5 to 5 ° 0.05 F002 0
" EBE5 PMU 1 Ia Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBE6 PMU 1 Ib Calibration Angle -5 to 5 ° 0.05 F002 0
" EBE7 PMU 1 Ib Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBE8 PMU 1 Ic Calibration Angle -5 to 5 ° 0.05 F002 0
" EBE9 PMU 1 Ic Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBEA PMU 1 Ig Calibration Angle -5 to 5 ° 0.05 F002 0
" EBEB PMU 1 Ig Calibration Magnitude 95 to 105 % 0.1 F002 1000
" EBEC PMU 1 Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0
" EBED PMU 1 Sequence Current Shift Angle -180 to 180 ° 30 F002 0
C60, N60 EBEE ...Repeated for PMU 2
N60 EC00 ...Repeated for PMU 3
" EC12 ...Repeated for PMU 4
" EC24 ...Repeated for PMU 5
" EC36 ...Repeated for PMU 6
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
C60, D60, F60,
G60, L30, L90,
N60, T60
EC48 PMU Network Reporting Function 0 to 1 --- 1 F102 0 (Disabled)
" EC49 PMU Network Reporting ID Code 1 to 65534 --- 1 F001 1
" EC4A PMU TCP Port Number 1 to 65535 --- 1 F001 4712
" EC4B PMU UDP Port Number 1 1 to 65535 --- 1 F001 4713
" EC4C PMU UDP Port Number 2 1 to 65535 --- 1 F001 4714
Settings File Template (Read/Write Setting)
All ED00 FlexLogic Displays Active 0 to 1 --- 1 F102 1 (Enabled)
" ED01 Template Access --- --- --- F205 (none)
Setting File Template (Read Only Non-Volatile)
All ED07 Last Settings Change Date 0 to 4294967295 --- 1 F050 0
Settings File Template (Read/Write Setting)
All ED09 Template Bitmask (750 items) 0 to 65535 --- 1 F001 0
Phasor Measurement Unit Records (Read Only)
C60, D60, F60,
G60, L30, L90,
N60, T60
EFFF PMU Recording Number of Triggers 0 to 65535 --- 1 F001 0
Products Address Register name Range Units Step Format Default