CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-211
2
F531
ENUMERATION: LANGUAGE
0 = English, 1 = French, 2 = Chinese, 3 = Russian, 4 = Turkish, 5 =
German
F534
ENUMERATION: 87PC TRIP SECURITY
0 = First Coincidence, 1 = Enhanced
F535
ENUMERATION: AUTOMATIC VOLTAGE REGULATOR
OPERATING SIGNAL
0 = Vab, 1 = Vbc, 2 = Vca, 3 = Vaver, 4 = V1, 5 = Vaux, 6 = Vag, 7 =
Vbg, 8 = Vcg
F536
ENUMERATION: AUTOMATIC VOLTAGE REGULATOR
CONTROL MODE
0 = Voltage, 1 = VAR
F537
ENUMERATION: AUTOMATIC VOLTAGE REGULATOR VAR
OPEN MODE
0 = Minimize uptime, 1 = Minimize number of operations
F540
ENUMERATION: PMU POST-FILTER
F542
ENUMERATION: PMU TRIGGERING MODE
0 = Automatic Overwrite, 1 = Protected
F543
ENUMERATION: PMU PHASORS
F544
ENUMERATION: PMU RECORDING/REPORTING RATE
F546
ENUMERATION: PMU REPORTING STYLE
0 = Polar, 1 = Rectangular
F547
ENUMERATION: PMU REPORTING FORMAT
0 = Integer, 1 = Floating
F548
ENUMERATION: PMU COMMUNICATION PROTOCOL
0 = NONE, 1 = 37.118, 2 = 90-5
F549
ENUMERATION: PMU PERFORMANCE CLASS
0 = None, 1 = M-CLASS, 2 = P-CLASS
131 32User PB 2 47User 7
14 2
Enumeration Filter
0None
1 10Hz/s<10Hz
2 10Hz/s<20Hz
3 20Hz/s<10Hz
4 20Hz/s<20Hz
Value Keypress Value Keypress Value Keypress
Value Phasor Value Phasor
0Off 8Ig
1Va 9V1
2Vb 10V2
3Vc 11V0
4Vx 12I1
5Ia 13I2
6Ib 14I0
7Ic
Value Rate Value Rate
0 1/second 7 20second
1 2/second 8 25/second
2 4/second 9 30/second
3 5/second 10 50/second
4 10/second 11 60/second
5 12/second 12 100/second
6 15/second 13 120/second