2-212 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
F550
ENUMERATION: RTD INPUT APPLICATION
F551
ENUMERATION: RTD TRIP VOTING
F552
ENUMERATION: RTD INPUT OPEN
F560
ENUMERATION: IN-ZONE TRANSFORMER CONNECTION
F561
ENUMERATION: 87L INRUSH INHIBIT MODE
F562
ENUMERATION: 87L IN-ZONE TRANSFORMER LOCATION
F563
ENUMERATION: DSCP TYPE
F600
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value to be used when
this parameter is selected. Only certain values can be used as
FlexAnalogs (basically all metering quantities used in protection).
Enumeration RTD input application
0None
1Stator
2Bearing
3Ambient
4Group 1
5Group 2
Enumeration RTD trip voting
0None
1Group
2RTD Input 1
3RTD Input 2
4RTD Input 3
5RTD Input 4
6RTD Input 5
7RTD Input 6
8RTD Input 7
9RTD Input 8
10 RTD Input 9
11 RTD Input 10
12 RTD Input 11
13 RTD Input 12
Enumeration RTD open
0None
1Alarm
2Block
Enumeration In-zone transformer connection
0None
10° lag
2 30° lag
3 60° lag
4 90° lag
5 120° lag
6 150° lag
7 180° lag
8 210° lag
9 240° lag
10 270° lag
11 300° lag
12 330° lag
Enumeration Inrush inhibit mode
0 Disabled
1 Per phase
2 Two out of three
3 Average
Enumeration In-zone transformer location
0Local-Tap
1 Remote 1-Tap
2 Remote 2-Tap
Enumeration DSCP type
0None
1 Expedited Forwarding