3-44 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.12 Breaker flashover (FlshOv)
This element is instantiated in the following products: B30, C60, C70, D60, F35, F60, G60, L60, L90, M60, T60.
Table 3-31: Breaker flashover data objects
setSrcRef ObjectReference SP BF# BKR POS2 φA/3P. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ05 ORG BF# BKR POS1 φB setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS1 φB. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ06 ORG BF# BKR POS1 φC setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS1 0C. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ07 ORG BF# BKR POS2 φB setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS2 φB. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ08 ORG BF# BKR POS2 φC setting for setting
group γ
R
setSrcRef ObjectReference SP BF# BKR POS2 φC. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
OpIn ACT BKR FAIL # RETRIP operands R
general BOOLEAN ST re-trip operand BKR FAIL #
RETRIP
R
phsA BOOLEAN ST re-trip operand BKR FAIL #
RETRIPA
R
phsB BOOLEAN ST re-trip operand BKR FAIL #
RETRIPB
R
phsC BOOLEAN ST re-trip operand BKR FAIL #
RETRIPC
R
BkrOp& SPS BKR FAIL # T& OP operand R
stVal BOOLEAN ST BKR FAIL # T& OP R
OpEx ACT BKR FAIL # TRIP OP operand R
general BOOLEAN ST trip operand BKR FAIL # TRIP OP R
InRefγ09 ORG BF# PH A INITIATE setting for setting
group γ
R
setSrcRef ObjectReference SP BF# PH A INITIATE. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ10 ORG BF# PH B INITIATE setting for setting
group γ
R
setSrcRef ObjectReference SP BF# PH B INITIATE. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ11 ORG BF# PH C INITIATE setting for setting
group γ
R
setSrcRef ObjectReference SP BF# PH C INITIATE. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: FlshOvPIOC# LDevice inst: Prot UR element: BREAKER FLASHOVER element #
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT BKR # FLSHOVR OP operand (including
individual three phases)
R
general BOOLEAN ST BKR # FLSHOVR OP R
phsA BOOLEAN ST BKR # FLSHOVR OP A R
phsB BOOLEAN ST BKR # FLSHOVR OP B R
phsC BOOLEAN ST BKR # FLSHOVR OP C R
Str ACD BKR # FLSHOVR PKP operand (including
individual three phases)
R
LNName: BkrFaRBRF# LDevice inst: Prot UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C