EasyManua.ls Logo

GE b30 - Page 305

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-67
3
3.5.2.32 Line pickup (LinPkp)
This element is instantiated in the following products: D30, D60, L60, L90.
Table 3-60: Line pickup data objects
3.5.2.33 Load encroachment (LodEn)
This element is instantiated in the following products: D30, D60, F60, L60, L90, T60.
Table 3-61: Load encroachment data objects
LNName: LinPkpPIOC1 LDevice inst: Prot UR element: Line Pickup functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD LINE PICKUP PKP operand R
general BOOLEAN ST LINE PICKUP PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT LINE PICKUP OP operand R
general BOOLEAN ST LINE PICKUP OP R
Dpo SPS LINE PICKUP DPO operand, which is the
inverse of LINE PICKUP PKP
R
stVal BOOLEAN ST LINE PICKUP DPO R
UnAφ SPS LINE PICKUP operand that activates on
phase θ current below 5% of nominal
R
stVal BOOLEAN ST LINE PICKUP I<θ R
UnV SPS LINE PICKUP UV PKP operand R
stVal BOOLEAN ST LINE PICKUP UV PKP R
LeoSt SPS LINE PICKUP LEO PKP operand R
stVal BOOLEAN ST LINE PICKUP LEO PKP R
Zn2Tr SPS LINE PICKUP RCL TRIP operand R
stVal BOOLEAN ST LINE PICKUP RCL TRIP R
BlkRefγ ORG LINE PICKUP BLOCK setting for setting
group γ.
R
setSrcRef ObjectReference SP LINE PICKUP BLOCK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LodEncPDIS1 LDevice inst: Prot UR element: LOAD ENCROACHMENT functions
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD LOAD ENCHR PKP operand R
general BOOLEAN ST LOAD ENCHR PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT LOAD ENCHR OP operand R
general BOOLEAN ST LOAD ENCHR OP R
Dpo SPS LOAD ENCHR DPO operand R
stVal BOOLEAN ST LOAD ENCHR DPO R
BlkRefγ ORG LOAD ENCRMNT BLK setting for setting
group γ.
R
GEORG R
setSrcRef ObjectReference SP LOAD ENCRMNT BLK for group γ.reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
LOAD ENCRMNT BLK for setting
group γ.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C

Table of Contents