3-84 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-88: Phase comparison fault detector high (FDH) data objects
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ2 ORG CHARGE COMPENST BLK setting of setting
group γ.
R
setSrcRef ObjectReference SP CHARGE COMPENST BLK setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
Str ACD 87PC PKP operand R
general BOOLEAN ST 87PC PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Dpo SPS 87PC DPO operand, which is the inverse
of 87PC PKP
R
stVal BOOLEAN ST 87PC DPO R
Op ACT 87PC OP operand R
general BOOLEAN ST 87PC OP R
FDLOp SPS 87PC FDL OP operand R
stVal BOOLEAN ST 87PC FDL OP R
TransBlk SPS 87PC TRANS BLOCK OP operand R
stVal BOOLEAN ST 87PC TRANS BLOCK OP R
RXζ SPS 87PC RXζ operand. R
stVal BOOLEAN ST 87PC RXζ R
CmpCtβI1 MV CT# COMP I1 Mag in amperes R
instMag AnalogueValue MX R
instMag.f FLOAT32 CT# COMP I1 Mag R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF PhCmp1PDIF1.CmpCt#I1.db R/W/C
zeroDb INT32U CF 0 R
CmpCt#I2 MV CT# COMP I2 Mag in amperes R
instMag AnalogueValue MX R
instMag.f FLOAT32 CT# COMP I2 Mag R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF PhCmp1PDIF1.CmpCt#I2. R/W/C
zeroDb INT32U CF 0 R
LNName: PhCmp2PDIF1 LDevice inst: Prot UR element: 87PC SCHEME specific to FDH element
data obj. data attribute Type FC UR Name Description R/W/C
InRefγ1 ORG 87PC FDH AUX setting of setting group γ.R
setSrcRef ObjectReference SP 87PC FDH AUX setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ2 ORG 87PC FDH SUPV setting of setting group
γ.
R
setSrcRef ObjectReference SP 87PC FDH SUPV setting reference to the data attribute to input R/C
LNName: PhCmp1PDIF1 LDevice inst: Prot UR element: 87PC SCHEME (except FDH element specifics) and Charging
Current Compensation element
data obj. data attribute Type FC UR Name Description R/W/C