CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-93
3
Table 3-105: Phase overvoltage data objects
3.5.2.60 Phase select (PhSel)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-106: Phase select data objects
LNName: PhsOvPTOV# LDevice inst: Prot UR element: Phase Overvoltage element # functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD PHASE OV # PKP operands (including
individual three phases)
R
general BOOLEAN ST PHASE OV # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsA BOOLEAN ST PHASE OV # PKP A R
dirPhsA ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsB BOOLEAN ST PHASE OV # PKP B R
dirPhsB ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsC BOOLEAN ST PHASE OV # PKP C R
dirPhsC ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT PHASE OV # OP operand (including
individual three phases)
R
general BOOLEAN ST PHASE OV # OP R
phsA BOOLEAN ST PHASE OV # OP A R
phsB BOOLEAN ST PHASE OV # OP B R
phsC BOOLEAN ST PHASE OV # OP C R
Dpo SPS PHASE OV # DPO operand, which is the
inverse of PHASE OV PKP
R
stVal BOOLEAN ST PHASE OV # DPO R
DpoPhsβ SPS PHASE OV# DPO β operand” (where β
refers to Phase-A, B or C)
R
stVal BOOLEAN ST PHASE OV# DPO β (where β
refers to Phase-A, B or C)
R
BlkRefγ ORG PHASE OV # BLK setting for setting group
γ.
R
setSrcRef ObjectReference SP PHASE OV # BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhSelGAPC1 LDevice inst: Prot UR element: Phase select element
data obj. data attribute Type FC UR Name Description R/W/C
FltAG SPS PHASE SELECT AG operand R
stVal BOOLEAN ST PHASE SELECT AG R
FltBG SPS PHASE SELECT BG operand R
stVal BOOLEAN ST PHASE SELECT BG R
FltCG SPS PHASE SELECT CG operand R
stVal BOOLEAN ST PHASE SELECT CG R
FltSLG SPS PHASE SELECT SLG operand R
stVal BOOLEAN ST PHASE SELECT SLG R
FltAB SPS PHASE SELECT AB operand R
stVal BOOLEAN ST PHASE SELECT AB R
FltBC SPS PHASE SELECT BC operand R
stVal BOOLEAN ST PHASE SELECT BC R
FltCA SPS PHASE SELECT CA operand R
stVal BOOLEAN ST PHASE SELECT CA R
FltABG SPS PHASE SELECT ABG operand R
stVal BOOLEAN ST PHASE SELECT ABG R
FltBCG SPS PHASE SELECT BCG operand R