CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-95
3
Table 3-108: Phase undervoltage data objects
3.5.2.63 Power swing detection (RPSB_)
This element is instantiated in the following products: D30, D60, G60, L60, L90, N60, T60.
Table 3-109: Power swing detection data objects
LNName: PhsUvPTUV# LDevice inst: Prot UR element: Phase Undervoltage element # functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD PHASE UV# PKP operands (including
individual three phases)
R
general BOOLEAN ST PHASE UV# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsA BOOLEAN ST PHASE UV# PKP A R
dirPhsA ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsB BOOLEAN ST PHASE UV# PKP B R
dirPhsB ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsC BOOLEAN ST PHASE UV# PKP C R
dirPhsC ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT PHASE UV# OP operand (including
individual three phases)
R
general BOOLEAN ST PHASE UV# OP R
phsA BOOLEAN ST PHASE UV# OP A R
phsB BOOLEAN ST PHASE UV# OP B R
phsC BOOLEAN ST PHASE UV# OP C R
Dpo SPS PHASE UV# DPO operand, which is the
inverse of PHASE UV PKP
R
stVal BOOLEAN ST PHASE UV# DPO R
DpoPhsβ SPS PHASE UV# DPO β operands” (where β
refers to Phase-A, B or C)
R
stVal BOOLEAN ST PHASE UV# DPO β (where β
refers to Phase-A, B or C)
R
BlkRefγ ORG PHASE UV# BLOCK setting for setting
group γ.
R
setSrcRef ObjectReference SP PHASE UV# BLOCK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PwrSwgRPSB1 LDevice inst: Prot UR element: Power Swing Detect element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD POWER SWING INCOMING operand R
general BOOLEAN ST POWER SWING INCOMING R
dirGeneral ENUMERATED ST 0 R
StrOutgoin
g
SPS POWER SWING OUTGOING operand R
stVal BOOLEAN ST POWER SWING OUTGOING R
Op ACT POWER SWING TRIP R
general BOOLEAN ST POWER SWING TRIP R
BlkZn SPS POWER SWING BLOCK operand R
stVal BOOLEAN ST POWER SWING BLOCK R
Z1Chr1 SPS POWER SWING OUTER operand R
stVal BOOLEAN ST POWER SWING OUTER R
Z1Chr2 SPS POWER SWING MIDDLE operand R
stVal BOOLEAN ST POWER SWING MIDDLE R
Z1Chr3 SPS POWER SWING INNER operand R
stVal BOOLEAN ST POWER SWING INNER R
TmStr2 SPS POWER SWING TMR2 PKP operand R