3.5.2.64 Restricted ground fault (RgDif)
This element is instantiated in the following products: F60, G30, G60, L90, T35, T60.
Table 3-110: Restricted ground fault data objects
stVal BOOLEAN ST POWER SWING TMR2 PKP R
TmStr3 SPS POWER SWING TMR3 PKP operand R
stVal BOOLEAN ST POWER SWING TMR3 PKP R
TmStr4 SPS POWER SWING TMR4 PKP operand R
stVal BOOLEAN ST POWER SWING TMR4 PKP R
Blk SPS POWER SWING UN/BLOCK operand R
stVal BOOLEAN ST POWER SWING UN/BLOCK R
DistDet SPS POWER SWING 50DD operand R
stVal BOOLEAN ST POWER SWING 50DD R
InRefγ2 ORG POWER SW I2 SUPV ENAB setting for
setting group γ.
R
setSrcRef ObjectReference SP POWER SW I2 SUPV ENAB
setting
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG POWER SWING BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP POWER SWING BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: RgDifPDIF# LDevice inst: Prot UR element: Restricted Ground Fault # function
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT RESTD GND FT# OP operands R
general BOOLEAN ST RESTD GND FT# OP R
Dpo SPS RESTD GND FT# DPO operand R
stVal BOOLEAN ST RESTD GND FT# DPO R
Str ACD RESTD GND FT# PKP operand R
general BOOLEAN ST RESTD GND FT# PKP R
dirGeneral ENUMERATED ST 1 is code for Forward R
DifAClc WYE Differential currents R
net CMV R
net.instCVal Vector MX R
net.instCVal.mag
.f
FLOAT32 RGF# DIFF Igd magnitude, in
primary amps
R
net.cVal Vector MX R
net.cVal.mag.f FLOAT32 RGF# DIFF Igd magnitude, in
primary amps, with deadband
R
net.units Unit CF R
net.units.SIUnit ENUMERATED 5, the code for amps R
net.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
net.db INT32U CF RgDifPDIF#.DifAClc.net.db R/W/C
net.zeroDb INT32U CF R
RstA WYE Restraint currents R
net CMV R
net.instCVal Vector MX R
net.instCVal.mag
.f
FLOAT32 RGF# RESTR Igr magnitude, in
primary amps
R
net.cVal Vector MX R
net.cVal.mag.f FLOAT32 RGF# RESTR Igr magnitude, in
primary amps, with deadband
R
net.units Unit CF R
LNName: PwrSwgRPSB1 LDevice inst: Prot UR element: Power Swing Detect element