3-100 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-114: Sensitive directional power stage 1 data objects
Table 3-115: Sensitive directional power stage 2 data objects
3.5.2.68 Speed 2 motor acceleration time (S2AcTm)
This element is instantiated in the following products: M60.
Table 3-116: Speed 2 acceleration time data objects
LNName: Sen1PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 1 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD DIR POWER # STG1 PKP operand, which
becomes On when the directional power
comparator has operated.
R
general BOOLEAN ST DIR POWER # STG1 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT DIR POWER # STG1 OP operand R
general BOOLEAN ST DIR POWER # STG1 OP R
Dpo SPS DIR POWER # STG1 DPO operand, which
is the inverse of DIR POWER STG1 OP
R
stVal BOOLEAN ST DIR POWER # STG1 DPO R
LNName: Sen2PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 2 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD DIR POWER # STG2 PKP operand, which
becomes On when the directional power
comparator has operated.
R
general BOOLEAN ST DIR POWER # STG2 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT DIR POWER # STG2 OP operand R
general BOOLEAN ST DIR POWER # STG2 OP R
Dpo SPS DIR POWER # STG2 DPO operand, which
is the inverse of DIR POWER STG2 OP
R
stVal BOOLEAN ST DIR POWER # STG2 DPO R
LNName: S2AcTmPMSS1 LDevice inst: Prot UR element: SPEED2 Acceleration Time element
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Op ACT MOTOR SPD2 ACL t OP operand R
general BOOLEAN ST MOTOR SPD2 ACL t OP R
Dpo SPS MOTOR SPD2 ACL t DPO operand R
stVal BOOLEAN ST MOTOR SPD2 ACL t DPO R
SPDTR SPS MOTOR SPD2 TR 2-1 OP operand R
stVal BOOLEAN ST MOTOR SPD2 TR 2-1 OP R
BlkRefγ ORG SPEED2 ACCEL BLOCK setting for setting
group γ.
R
GEORG R
setSrcRef ObjectReference SP SPEED2 ACCEL BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
SPEED2 ACCEL BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C