3-110 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-128: Undercurrent data objects
3.5.2.79 Underfrequency (UnHz)
This element is instantiated in the following products: D30, D60, F35, F60, G30, G60, L30, L90, M60, N60, T35, T60.
Table 3-129: Underfrequency data objects
3.5.2.80 Underpower (UnPwr)
This element is instantiated in the following products: M60.
Table 3-130: Underpower data objects
LNName: UnCurPTUC1 LDevice inst: Prot UR element: Undercurrent element
data obj. data attribute Type FC UR Name Description R/W/C
StrAlm ACD U/CURR ALARM PKP operand R
general BOOLEAN ST U/CURR ALARM PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Str ACD U/CURR TRIP PKP operand R
general BOOLEAN ST U/CURR TRIP PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
OpAlm ACT U/CURR ALARM OP operand R
general BOOLEAN ST U/CURR ALARM OP R
Op ACT U/CURR TRIP OP operand R
general BOOLEAN ST U/CURR TRIP OP R
BlkRefγ ORG UNDERCURRENT BLOCK setting in setting
group γ
R
setSrcRef ObjectReference SP UNDERCURRENT BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: UnHzPTUF# LDevice inst: Prot UR element: Underfrequency element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD UNDERFREQ # PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST UNDERFREQ # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT UNDERFREQ # OP operand R
general BOOLEAN ST UNDERFREQ # OP R
Dpo SPS UNDERFREQ # DPO operand R
stVal BOOLEAN ST UNDERFREQ # DPO R
BlkRef1 ORG UNDERFREQ # BLOCK setting. R
setSrcRef ObjectReference SP UNDERFREQ # BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: UnPwrPDUP# LDevice inst: Prot UR element: Under Power element
data obj. data attribute Type FC UR Name Description R/W/C
StrAlm ACD UNDERPWR # ALARM PKP operand R
general BOOLEAN ST UNDERPWR # ALARM PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Str ACD UNDERPWR # TRIP PKP operand R
general BOOLEAN ST UNDERPWR # TRIP PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
OpAlm ACT UNDERPWR # ALARM OP operand R
general BOOLEAN ST UNDERPWR # ALARM OP R
Op ACT UNDERPWR # TRIP OP operand R

Table of Contents