EasyManua.ls Logo

GE b30 - Page 354

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-116 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-141: Breaker arcing current phase data objects
stVal BOOLEAN ST BKR ARC # MAX DPO R
InRef1 ORG BKR # CLR ARC AMPS setting R
setSrcRef ObjectReference SP BKR # CLR ARC AMPS reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG BKR # ARC AMP BLOCK setting R
setSrcRef ObjectReference SP BKR # ARC AMP BLOCK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
ColOpn SPS Logical OR of status value of mapped
FlexLogic operands in BKR # ARC AMP
INT- A, BKR # ARC AMP INT- B, BKR # ARC
AMP INT- C
R
stVal BOOLEAN ST Logical OR condition to
CBArc1SCBR#.ColOpn,
CBArc2SCBR#.ColOpn,
CBArc3SCBR#.ColOpn
R
OpTmOpn MV BKR # OPERATING TIME in ms R
instMag AnalogueValue MX R
instMag.f FLOAT32 Mapped BKR # OPERATING TIME R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED -3, the code for a multiplier of 1/1000 R
db INT32 CF CBArc0SCBR#.OpTmOpn.db R/W/C
zeroDb INT32 CF 0 R
MemClr SPC CLEAR BREAKER # ARCING AMPS
command
R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF CBArc0SCBR#.MemClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
LNName: CBArcΘSCBR# LDevice inst: Ctrl UR element: BREAKER # ARCING CURRENT element
data obj. data attribute Type FC UR Name Description R/W/C
ColOpn SPS Status value of mapped FlexLogic
operand in BKR # ARC AMP INT- ψ
R
stVal BOOLEAN ST Status value of mapped
FlexLogic operand in BKR # ARC
AMP INT- ψ setting
R
InRef1 ORG BKR # ARC AMP INT-µ setting R
setSrcRef ObjectReference SP BKR # ARC AMP INT- µ reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
AccAbr MV BKR # ACC ARCING AMP ψ in A2s R
instMag AnalogueValue MX R
instMag.f FLOAT32 BKR # ACC ARCING AMP ψ R
mag Analogue Value MX R
LNName: CBArc0SCBR# LDevice inst: Ctrl UR element: BREAKER # ARCING CURRENT element
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals