EasyManua.ls Logo

GE b30 - Page 355

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-117
3
3.5.3.6 Breaker restrike (BkrRtk)
This element is instantiated in the following products: B30, C60, C70, D60, F35, F60, G60, L60, L90, M60, T60.
Table 3-142: Breaker restrike data objects
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 70, the code for Amps Squared time (A2t) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF CBArcΘSCBR#.AccAbr.db R/W/C
zeroDb INT32 CF 0 R
SwA MV BKR 1 ARCING AMP ψ in A2s R
instMag AnalogueValue MX R
instMag.f FLOAT32 BKR 1 ARCING AMP ψ R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 70, the code for Amps Squared time (A2t) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF CBArcΘSCBR#.SwA.db R/W/C
zeroDb INT32 CF 0 R
MaxIntrA MV BKR 1 AMP MAX ψ R
instMag AnalogueValue MX R
instMag.f FLOAT32 BKR 1 AMP MAX ψ R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for ampere R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF CBArcΘSCBR#.MaxIntrA.db R/W/C
zeroDb INT32 CF 0 R
RctTmOpn MV BKR # OPERATING TIME ψ in ms R
instMag AnalogueValue MX R
instMag.f FLOAT32 Mapped BKR # OPERATING TIME
ψ
R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED -3, the code for a multiplier of 1/1000 R
db INT32 CF CBArcΘSCBR#.RctTmOpn.db R/W/C
zeroDb INT32 CF 0 R
LNName: BkrRtkPIOC# LDevice inst: Ctrl UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
LNName: CBArcΘSCBR# LDevice inst: Ctrl UR element: BREAKER # ARCING CURRENT element
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals