EasyManua.ls Logo

GE b30 - Page 362

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-124 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.10 Cold load pickup (Cold)
This element is instantiated in the following products: F35, F60.
Table 3-146: Cold load pickup data objects
3.5.3.11 CT failure detector (CtFail)
This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60.
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef26 ORG CAP # BKR OPEN 52b setting. R
setSrcRef ObjectReference SP CAP # BKR OPEN 52b setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef27 ORG CAP # REMOTE CLOSE setting. R
setSrcRef ObjectReference SP CAP # REMOTE CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef28 ORG CAP # LOCAL CLOSE setting. R
setSrcRef ObjectReference SP CAP # LOCAL CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef29 ORG CAP # AUTO CLOSE setting. R
setSrcRef ObjectReference SP CAP # AUTO CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef30 ORG CAP # BKR CLSD 52a setting. R
setSrcRef ObjectReference SP CAP # BKR CLSD 52a setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG CAP # BKR CLOSE BLK setting. R
setSrcRef ObjectReference SP CAP # BKR CLOSE BLK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef31 ORG CAP # CLS OVERRIDE setting. R
setSrcRef ObjectReference SP CAP # CLS OVERRIDE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: ColdFXUT# LDevice inst: Ctrl UR element: Cold Load Pickup # element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT COLD LOAD # OP operand R
general BOOLEAN ST COLD LOAD # OP R
StrVal ASG Start level of the current, which is fixed at
2% of Nominal CT (0.02 pu), and it is non-
configurable read only value
R
setMag AnalogueValue SP R
setMag.f FLOAT32 0.02 R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
BlkRef1 ORG COLD LOAD # BLK setting R
setSrcRef ObjectReference SP COLD LOAD # BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1 ORG COLD LOAD # INIT setting R
setSrcRef ObjectReference SP COLD LOAD # INIT. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: CapCtlGAPC# LDevice inst: Ctrl UR element: Capacitor control element #
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals