3-124 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.10 Cold load pickup (Cold)
This element is instantiated in the following products: F35, F60.
Table 3-146: Cold load pickup data objects
3.5.3.11 CT failure detector (CtFail)
This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60.
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef26 ORG CAP # BKR OPEN 52b setting. R
setSrcRef ObjectReference SP CAP # BKR OPEN 52b setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef27 ORG CAP # REMOTE CLOSE setting. R
setSrcRef ObjectReference SP CAP # REMOTE CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef28 ORG CAP # LOCAL CLOSE setting. R
setSrcRef ObjectReference SP CAP # LOCAL CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef29 ORG CAP # AUTO CLOSE setting. R
setSrcRef ObjectReference SP CAP # AUTO CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef30 ORG CAP # BKR CLSD 52a setting. R
setSrcRef ObjectReference SP CAP # BKR CLSD 52a setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG CAP # BKR CLOSE BLK setting. R
setSrcRef ObjectReference SP CAP # BKR CLOSE BLK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef31 ORG CAP # CLS OVERRIDE setting. R
setSrcRef ObjectReference SP CAP # CLS OVERRIDE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: ColdFXUT# LDevice inst: Ctrl UR element: Cold Load Pickup # element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT COLD LOAD # OP operand R
general BOOLEAN ST COLD LOAD # OP R
StrVal ASG Start level of the current, which is fixed at
2% of Nominal CT (0.02 pu), and it is non-
configurable read only value
R
setMag AnalogueValue SP R
setMag.f FLOAT32 0.02 R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
BlkRef1 ORG COLD LOAD # BLK setting R
setSrcRef ObjectReference SP COLD LOAD # BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1 ORG COLD LOAD # INIT setting R
setSrcRef ObjectReference SP COLD LOAD # INIT. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: CapCtlGAPC# LDevice inst: Ctrl UR element: Capacitor control element #
data obj. data attribute Type FC UR Name Description R/W/C