CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-125
3
Table 3-147: CT fail data objects
3.5.3.12 CT trouble (CtTb)
This element is instantiated in the following products: B30, B90.
Table 3-148: CT trouble data objects
3.5.3.13 Digitizers (Dgtzr)
This element is instantiated in the following products: N60.
Table 3-149: Digitizer data objects
3.5.3.14 Fault location (FltRpt)
This element is instantiated in the following products: C60, D30, D60, F35, F60, L30, L60, L90.
LNName: CtFailPIOC# LDevice inst: Ctrl UR element: CT failure detector # element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD CT FAIL # PKP operand, which indicated
Op will operate when delay expires
R
general BOOLEAN ST CT FAIL # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown R
Op ACT CT FAIL # OP operand R
general BOOLEAN ST CT FAIL # OP R
BlkRef1 ORG CT FAIL # BLOCK setting R
setSrcRef ObjectReference SP CT FAIL # BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: CtTbPIOC# LDevice inst: Ctrl UR element: CT Trouble Zone # element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT CT TROUBLE ZONE # OP operands
(including individual three phases)
R
general BOOLEAN ST CT TROUBLE #1 OP R
phsA BOOLEAN ST CT TROUBLE # OP A R
phsB BOOLEAN ST CT TROUBLE # OP B R
phsC BOOLEAN ST CT TROUBLE # OP C R
LNName: DgtzrGAPC# LDevice inst: Ctrl UR element: Digitizer #
data obj. data attribute Type FC UR Name Description R/W/C
IndΘ SPS DIGITIZER # BIT Θ operand value R
stVal BOOLEAN ST DIGITIZER # BIT Θ R
Out MV DIGITIZER # Out Value R
instMag AnalogueValue MX R
instMag.f FLOAT32 DIGITIZER # Out Value R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for multiplier 1 R
db INT32U CF DgtzrGAPC#.Out.db R/W/C
zeroDb INT32U CF 0 R
InRef1 ORG DIGITIZER # SOURCE setting. R
setSrcRef ObjectReference SP DIGITIZER # SOURCE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C