3-126 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-150: Fault report settings data objects
Table 3-151: Fault report data file data objects
LNName: FltRptRFLO#LDevice inst: CtrlUR element: FAULT REPORT # settings
data obj. data attribute Type FC UR Name Description R/W/C
TapLocFlt SPS TAP-LOCAL FAULT operand R
stVal BOOLEAN ST TAP-LOCAL FAULT R
NumRcd
INS
Actual number of records
R
stVal INT32 ST Modbus register 3020h, I.e.,
“Number of Fault Reports”
R
FltZ CMV Mandatory data attribute which in this
case is fixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 0 R
cVal.ang.f FLOAT32 0 R
RsStat SPC instantiated only in FltRptRFLO1 R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDurINT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF
FltRptRFLO1.RsStat
.ctlModel R/W/C
sboT
imeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operT
imeout INT32U CF 0 R
InRef1 ORG FAULT REPORT# TRIG. R
setSrcRef ObjectReference SP FAULT REPORT# TRIG. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG Only instantiated in FltRptRFLO1 R
setSrcRef ObjectReference SP CLEAR FAULT REPORTS. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: FltRFLOψψLDevice inst: CtrlUR element: Selected values from Fault Report Data
f
ile ψψ
data obj. data attribute Type FC UR Name Description R/W/C
FltZ CMV Mandatory data attribute which in this
case is f ixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 Fault impedance magnitude in
primary ohms calculated as
shown below
R
cVal.ang.f FLOAT32 Fault impedance angle in
degrees calculated as shown
below
R
FltRis MV FAULTψψ FAULT RESIST converted to
primary ohms
R
mag AnalogueValue MX R
mag.f FLOAT32 Actual Value FAULTψψ FAULT
RESIST converted to primary
ohms
R
units Unit CF R
units.SIUnit ENUMERATED 30, the code for primary electric
resistance in ohm (V/A)
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
FltLoopRis MV FAULTψψ LOOP RESIST converted to
primary ohms
R
mag AnalogueValue MX R

Table of Contents