CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-127
3
3.5.3.15 Frequency out-of-band accumulation (HzBnd)
This element is instantiated in the following products: G30, G60.
Table 3-152: Frequency out-of-band accumulation data objects
Table 3-153: Frequency out-of-band accumulation prefix instance number $ data objects
3.5.3.16 High-impedance fault detection (HiZ)
This element is instantiated in the following products: F60.
Table 3-154: Hi-Z data objects
LNName: HzBndPTUF1 LDevice inst: Ctrl UR element: Frequency OOB Accumulation element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FREQ OOB ACCUM PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST FREQ OOB ACCUM PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT FREQ OOB ACCUM OP operand R
general BOOLEAN ST FREQ OOB ACCUM OP R
BlkRef1 ORG FREQ ACCUM BLOCK setting. R
setSrcRef ObjectReference SP FREQ ACCUM BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: HzBnd$PTUF1 LDevice inst: Ctrl UR element: Frequency OOB Accumulator $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FREQ OOB BAND $ PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST FREQ OOB BAND $ PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT FREQ OOB BAND $ OP operand R
general BOOLEAN ST FREQ OOB BAND $ OP R
Dpo SPS FREQ OOB BAND $ DPO operand R
stVal BOOLEAN ST FREQ OOB BAND $ DPO R
HzObAccu
m
MV FREQUENCY OOB BAND $
ACCUMULATION in percentage (%)
R
instMag AnalogueValue MX R
instMag.f FLOAT32 FREQUENCY OOB BAND $
ACCUMULATION
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED -2 is code for percent R
db INT32 CF HzBnd$PTUF1.HzObAccum.db R/W/C
zeroDb INT32 CF 0 R
LNName: HiZPHIZ1 LDevice inst: Ctrl UR element: HI-Z function
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD HI-Z ARMED operand R
general BOOLEAN ST HI-Z ARMED R
dirGeneral ENUMERATED ST 0, the code for unknown It is unknown as
the element is non-directional.
R
Op ACT HI-Z ARC DETECTED operand including
Phases-A, B, C and Neutral
R
general BOOLEAN ST HI-Z ARC DETECTED R