3-128 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
phsA BOOLEAN ST HI-Z ARC DETECTED-A R
phsB BOOLEAN ST HI-Z ARC DETECTED-B R
phsC BOOLEAN ST HI-Z ARC DETECTED-C R
neut BOOLEAN ST HI-Z ARC DETECTED-N R
Dpo SPS HI-Z ARC DETECTED DPO operand R
stVal BOOLEAN ST HI-Z ARC DETECTED DPO R
DisArmed SPS HI-Z DISARMED operand R
stVal BOOLEAN ST HI-Z DISARMED R
DwnCond ACT HI-Z DOWNED COND operand including
phsA, B, C and Neutral
R
general BOOLEAN ST HI-Z DOWNED COND R
phsA BOOLEAN ST HI-Z DOWNED COND-A R
phsB BOOLEAN ST HI-Z DOWNED COND-B R
phsC BOOLEAN ST HI-Z DOWNED COND-C R
neut BOOLEAN ST HI-Z DOWNED COND-N R
ArcSuspect ACT HI-Z ARC SUSPECTED operand including
Phases-A, B, C and Neutral
R
general BOOLEAN ST HI-Z ARC SUSPECTED R
phsA BOOLEAN ST HI-Z ARC SUSPECTED-A R
phsB BOOLEAN ST HI-Z ARC SUSPECTED-B R
phsC BOOLEAN ST HI-Z ARC SUSPECTED-C R
neut BOOLEAN ST HI-Z ARC SUSPECTED-N R
HiZIOC ACT HI-Z IOC operand including Phases A, B,
C.
R
general BOOLEAN ST OR logic of operands (HI-Z IOC A
or HI-Z IOC B or HI-Z IOC C)
R
phsA BOOLEAN ST HI-Z IOC A R
phsB BOOLEAN ST HI-Z IOC B R
phsC BOOLEAN ST HI-Z IOC C R
neut BOOLEAN ST HI-Z IOC N R
LossLd ACT HI-Z LOSS OF LOAD operand including
Phases A, B, C.
R
general BOOLEAN ST OR logic of operands HI-Z LOSS
OF LOAD-A or HI-Z LOSS OF
LOAD–B or HI-Z LOSS OF LOAD-C
R
phsA BOOLEAN ST HI-Z LOSS OF LOAD-A R
phsB BOOLEAN ST HI-Z LOSS OF LOAD–B R
phsC BOOLEAN ST HI-Z LOSS OF LOAD-C R
HiZSt ENS HIZ STATUS actual value R
stVal ENUMERATED ST HIZ STATUS, where 0 = Normal, 1
= Coordination Timeout, 2 =
Armed, 5 = Arcing, 9 = Downed
Conductor, actual values
R
ArcConfid
Φ
INS HIZ Phase Φ Arc Conf Actual Value R
stVal INT32 ST HIZ Phase Φ Arc Conf in
percentage
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
Trigger1$ ENS HIZ RECORDS, HIZ $ actual value R
stVal ENUMERATED ST HI-Z Capture $ Trigger Type,
where 0 = None, 1 = Loss of
Load, 2 = Arc Suspected, 3 =
Arcing, 4 = Overcurrent, 5 =
Down Conductor, 6 = External
R
Trigger2$ ENS HIZ RECORDS, RMS $ actual value R
LNName: HiZPHIZ1 LDevice inst: Ctrl UR element: HI-Z function
data obj. data attribute Type FC UR Name Description R/W/C