3-134 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.20 Reduced voltage starting (LoVStr)
This element is instantiated in the following products: M60.
Table 3-158: Reduced voltage starting data objects
3.5.3.21 Restart delay (StrDl)
This element is instantiated in the following products: M60.
Table 3-159: Restart delay data objects
setSrcRef ObjectReference SP PID # TRACKING SIGNAL setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG PID # BLK setting. R
setSrcRef ObjectReference SP PID # BLK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LoVStrGAPC1 LDevice inst: Ctrl UR element: REDUCED VOLTAGE STARTING element
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD Mandatory data object which in this case
is fixed at false
R
general BOOLEAN ST R
dirGeneral ENUMERATED ST 0 R
Op ACT REDUCED VOLT OP operand R
general BOOLEAN ST REDUCED VOLT OP R
Ctrl SPS REDUCED VOLT CTRL operand R
stVal BOOLEAN ST REDUCED VOLT CTRL operand R
BlkRef1 ORG REDUCED VOLT BLOCK setting. R
GEORG R
setSrcRef ObjectReference SP REDUCED VOL BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
REDUCED VOL BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: StrDlPMRI1 LDevice inst: Ctrl UR element: RESTART DELAY element
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
StrInh SPS RESTART TIME OP operand R
stVal BOOLEAN ST RESTART TIME OP R
LNName: PIDRegFPID# LDevice inst: Ctrl UR element: PID Regulator element #
data obj. data attribute Type FC UR Name Description R/W/C