CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-135
3
3.5.3.22 Single pole autoreclose (Rec13p)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-160: Single pole autoreclose data objects
BlkRef1 ORG RESTART DELAY BLK setting R
GEORG R
setSrcRef ObjectReference SP RESTART DELAY BLK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
RESTART DELAY BLK..
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
StrInhTmm INS RESTART DELAY LO TIME in Sec R
stVal INT32 ST RESTART DELAY LO TIME divided
by 60 to convert seconds to
minutes.
R
LNName: Rec13pRREC1 LDevice inst: Ctrl UR element: Autoreclose element
data obj. data attribute Type FC UR Name Description R/W/C
TrBeh ENS AR FORCE 3-P TRIP operand R
stVal ENUMERATED ST 3 if operand AR FORCE 3-P TRIP is On, 2
otherwise.
R
RecCyc INS AUTORECLOSE SHOT COUNT actual value R
stVal INT32 ST AUTORECLOSE SHOT COUNT R
AutoRecSt ENS Autoreclosing status R
stVal ENUMERATED ST R
Ena1 SPS AR ENABLED operand R
stVal BOOLEAN ST AR ENABLED R
Disabled SPS AR DISABLED operand R
stVal BOOLEAN ST AR DISABLED R
ArRip SPS AR RIP operand R
stVal BOOLEAN ST AR RIP R
P1Rip SPS AR 1-P RIP operand R
stVal BOOLEAN ST AR 1-P RIP R
P3Rip1 SPS AR 3-P/1 RIP operand R
stVal BOOLEAN ST AR 3-P/1 RIP R
P3Rip2 SPS AR 3-P/2 RIP operand R
stVal BOOLEAN ST AR 3-P/2 RIP R
P3Rip3 SPS AR 3-P/3 RIP operand R
stVal BOOLEAN ST AR 3-P/3 RIP R
P3Rip4 SPS AR 3-P/4 RIP operand R
stVal BOOLEAN ST AR 3-P/4 RIP R
ArLO SPS AR LO operand R
stVal BOOLEAN ST AR LO R
ArBlk1 SPS AR BKR1 BLK operand R
stVal BOOLEAN ST AR BKR1 BLK R
ArBlk1 SPS AR BKR2 BLK operand R
LNName: StrDlPMRI1 LDevice inst: Ctrl UR element: RESTART DELAY element