CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-137
3
3.5.3.23 Synchrocheck (SynChk)
This element is instantiated in the following products: C60, D30, D60, F60, G30, G60, L30, L60, L90, N60, T60.
Table 3-161: Synchrocheck data objects
setSrcRef ObjectReference SP AR BKR MAN CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef07 ORG AR 1P INIT setting R
setSrcRef ObjectReference SP AR 1P INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef08 ORG AR 3P INIT setting R
setSrcRef ObjectReference SP AR 3P INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef09 ORG AR 3P TD INIT setting R
setSrcRef ObjectReference SP AR 3P TD INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef10 ORG AR MULTI-P FAULT setting R
setSrcRef ObjectReference SP AR MULTI-P FAULT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef11 ORG BKR ONE POLE OPEN setting R
setSrcRef ObjectReference SP BKR ONE POLE OPEN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef12 ORG BKR 3 POLE OPEN setting R
setSrcRef ObjectReference SP BKR 3 POLE OPEN setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef13 ORG AR EXTEND DEAD T 1 setting R
setSrcRef ObjectReference SP AR EXTEND DEAD T 1setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef14 ORG AR RESET setting R
setSrcRef ObjectReference SP AR RESET setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef15 ORG AR BKR CLOSED setting R
setSrcRef ObjectReference SP AR BKR CLOSED setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG AR BLOCK setting R
setSrcRef ObjectReference SP AR BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef17 ORG AR PAUSE setting R
setSrcRef ObjectReference SP AR PAUSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef3 ORG AR BLOCK BKR2 setting R
setSrcRef ObjectReference SP AR BLOCK BKR2 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef19 ORG AR BUS FLT INIT setting R
setSrcRef ObjectReference SP AR BUS FLT INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: SynChkRSYN# LDevice inst: Ctrl UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
LNName: Rec13pRREC1 LDevice inst: Ctrl UR element: Autoreclose element
data obj. data attribute Type FC UR Name Description R/W/C