3-138 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Rel SPS SYNC # CLS OP operand, which becomes
On all synchrocheck criteria are fulfilled.
R
stVal BOOLEAN ST SYNC # CLS OP R
RelDpo SPS SYNC # CLS DPO operand, which
becomes Off when all synchrocheck
criteria are fulfilled.
R
stVal BOOLEAN ST SYNC # CLS DPO R
LivV1 SPS SYNC # V1 ABOVE MIN operand, which
indicates that V1 is above the LivVal1
setting.
R
stVal BOOLEAN ST SYNC # V1 ABOVE MIN R
DeaV1 SPS SYNC # V1 BELOW MAX operand, which
indicates that V1 is below the DeaVal1
setting.
R
stVal BOOLEAN ST SYNC # V1 BELOW MAX R
LivV2 SPS SYNC # V2 ABOVE MIN operand, which
indicates that V1 is above the LivVal2
setting.
R
stVal BOOLEAN ST SYNC # V2 ABOVE MIN R
DeaV2 SPS SYNC # V2 BELOW MAX operand, which
indicates that V2 is below the DeaVal1
setting.
R
stVal BOOLEAN ST SYNC # V2 BELOW MAX R
LivDea SPS SYNC # DEAD S OP operand, which
indicates that live/dead conditions have
been met.
R
stVal BOOLEAN ST SYNC # DEAD S OP R
LivDeaDpo SPS SYNC # DEAD S DPO operand, which
indicates that live/dead conditions have
not been met.
R
stVal BOOLEAN ST SYNC # DEAD S DPO R
LivLiv SPS SYNC # SYNC OP operand, which
indicates that both sources are live, and
that angle, frequency and voltage
difference and range conditions have
been met.
R
stVal BOOLEAN ST SYNC # SYNC OP R
LivLivDpo SPS SYNC # SYNC DPO operand, which
indicates that that one or both sources
are not live, or that angle, frequency and
voltage difference and range conditions
have been met.
R
stVal BOOLEAN ST SYNC # SYNC DPO R
DynOp SPS SYNC# S-CLOSE OP operand, which
becomes on when all criteria for dynamic
mode are fulfilled
R
stVal BOOLEAN ST SYNC# S-CLOSE OP R
DynDpo SPS SYNC# S-CLOSE DPO operand, which
becomes off when all criteria for dynamic
mode are fulfilled
R
stVal BOOLEAN ST SYNC# S-CLOSE DPO R
DynArmd SPS SYNC# S-CLOSE ARMD operand, which
becomes on when dynamic mode is
armed
R
stVal BOOLEAN ST SYNC# S-CLOSE ARMD R
DifVClc MV SYNCHROCHECK # DELTA VOLT, in primary
volts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SYNCHROCHECK 1 DELTA VOLT R
LNName: SynChkRSYN# LDevice inst: Ctrl UR element: Synchrocheck element # (ANSI 25)
data obj. data attribute Type FC UR Name Description R/W/C