CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-145
3
3.5.3.30 User-programmable fault report (UFlt)
This element is instantiated in the following products: B30 B90 C70 G30 G60 M60 N60 T35 T60.
Table 3-168: User-programmable fault report data objects
general BOOLEAN ST XFMR LIFE LOST OP R
Str ACD XFMR LIFE LOST PKP operand R
general BOOLEAN ST XFMR LIFE LOST PKP R
dirGeneral ENUMERATED ST 0 R
LosLifeRte MV DAILY RATE LOL actual Values. R
instMag AnalogueValue MX R
instMag.f FLOAT32 DAILY RATE LOL R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for second R
units.multiplier ENUMERATED 0 is multiplier for 1 R
db INT32 CF LosLifSPTR1.LosLifeRte.db R/W/C
zeroDb INT32 CF 0 R
LosLife MV XFMR LIFE LOST actual Values. R
instMag AnalogueValue MX R
instMag.f FLOAT32 XFMR LIFE LOST R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for second R
units.multiplier ENUMERATED 0 is multiplier for 1 R
db INT32 CF LosLifSPTR1.LosLife.db R/W/C
zeroDb INT32 CF 0 R
BlkRefγ ORG LOSS OF LIFE BLOCK for setting group γ.R
setSrcRef ObjectReference SP LOSS OF LIFE BLOCK for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: UFltRFLO# LDevice inst: ctrl UR element: USER PROGRAMMABLE FAULT REPORT # settings
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
FltZ CMV Mandatory data attribute which in this
case is fixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 0 R
cVal.ang.f FLOAT32 0 R
FltDiskm MV Mandatory data object which in this case
is fixed at zero
R
mag Analogue Value MX R
mag.f FLOAT32 0 R
InRef1 ORG PRE-FAULT # TRIGGER. R
GEORG R
LNName: LosLifSPTR1 LDevice inst: Ctrl UR element: Loss of Life Function
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents