3-146 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-169: User-programmable fault report actual values and clear data objects
setSrcRef ObjectReference SP PRE-FAULT # TRIGGER. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting PRE-
FAULT # TRIGGER.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef2 ORG FAULT # TRIGGER. R
GEORG R
setSrcRef ObjectReference SP FAULT # TRIGGER. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
FAULT # TRIGGER.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: UFlt0RFLO1 LDevice inst: ctrl UR element: USER PROGRAMMABLE FAULT REPORT actual values and clear
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
FltZ CMV Mandatory data attribute which in this
case is fixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 0 R
cVal.ang.f FLOAT32 0 R
FltDiskm MV Mandatory data object which in this case
is fixed at zero
R
mag Analogue Value MX R
mag.f FLOAT32 0 R
FltNum INS NEWEST RECORD NUMBER R
stVal INT32 ST NEWEST RECORD NUMBER R
units UNIT CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
LastClrTm INS LAST CLEARED DATE actual value R
stVal INT32 ST LAST CLEARED DATE actual value R
units Unit CF R
units.SIUnit ENUMERATED 4 R
LNName: UFltRFLO# LDevice inst: ctrl UR element: USER PROGRAMMABLE FAULT REPORT # settings
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents