CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-153
3
setSrcRef ObjectReference SP BREAKER # EXT ALARM reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by BREAKER #
EXT ALARM setting
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef6 ORG BREAKER # OUT OF SV (out-of-service)
setting.
R
GEORG R
setSrcRef ObjectReference SP BREAKER # OUT OF SV reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
BREAKER # OUT OF SV
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef7 ORG XCBR# ST.LOC OPERAND (local control)
setting.
R
GEORG R
setSrcRef ObjectReference SP XCBR# ST.LOC OPERAND reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
XCBR# ST.LOC OPERAND
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef8 ORG BREAKER # RACKED-IN setting. R
GEORG R
setSrcRef ObjectReference SP BREAKER # RACKED-IN reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
BREAKER # RACKED-IN
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: Bkr0XCBR# LDevice inst: System UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C