3-154 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-174: Breaker control data objects
LNName: BkrΘXCBR# LDevice inst: System UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Loc SPS Value of operand selected by setting
XCBR# ST.LOC OPERAND
R
stVal BOOLEAN ST Bkr0XCBR#.Loc.stVal R
OpCnt INS Phase ψ breaker operations counter. R
stVal INT32 ST R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
BadSt1 SPS BREAKER # ψ BAD ST operand R
stVal BOOLEAN ST BREAKER # ψ BAD ST R
ClsSt1 SPS BREAKER # ψ CLSD operand R
stVal BOOLEAN ST BREAKER # ψ CLSD R
OpnSt1 SPS BREAKER # ψ OPEN operand R
stVal BOOLEAN ST BREAKER # ψ OPEN R
IntermSt1 SPS BREAKER # ψ INTERM operand R
stVal BOOLEAN ST BREAKER # ψ INTERM R
Pos DPC Breaker φψ position status R
stVal CODED ENUM ST R
ctlModel CtlModels CF 0 R
BlkOpn SPC Breaker open commands blocked from
all sources including protection
R
stVal BOOLEAN ST Bkr0XCBR#.BlkOpn.stVal R
ctlModel CtlModels CF 0 R
BlkCls SPC Breaker close commands blocked from
all sources including protection
R
stVal BOOLEAN ST Bkr0XCBR#.BlkCls.stVal R
ctlModel CtlModels CF 0 R
CBOpCap INS Mandatory data object which in this case
is fixed at 3
R
stVal ENUMERATED ST 3 R
InRef1 ORG BREAKER # φA/3P CLSD setting” if Θ=”1”,
“BREAKER # φB CLSD setting” if Θ=”2”, or
“BREAKER # φC CLSD setting” if Θ=”3
R
GEORG R
setSrcRef ObjectReference SP BREAKER # φA/3P CLSD if Θ=”1”,
BREAKER # φB CLSD if Θ=”2”, or
BREAKER # φC CLSD if Θ=”3”
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R