CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-155
3
3.5.4.4 B90 isolator monitoring (B_Iso)
This element is instantiated in the following products: B90.
Table 3-175: B90 isolator monitoring data objects
3.5.4.5 Contact input interface (ConIn)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-176: Contact input data objects
InRef2 ORG BREAKER # φA/3P OPND setting” if Θ=”1”,
“BREAKER # φB OPND setting” if Θ=”2”, or
“BREAKER # φC OPND setting” if Θ=”3
R
GEORG R
setSrcRef ObjectReference SP BREAKER # φA/3P OPND if Θ=”1”,
BREAKER # φB OPND if Θ=”2”, or
BREAKER # φC OPND if Θ=”3”
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: B_IsoSSWI# LDevice inst: System UR element: B90 ISOLATOR # function
data obj. data attribute Type FC UR Name Description R/W/C
OpTmAlm SPS ISOLATOR # ALARM operand. R
stVal BOOLEAN ST ISOLATOR # ALARM R
IsoPos ACT ISOLATOR # POSITION operand. R
general BOOLEAN ST ISOLATOR # POSITION R
IsoBlk ACT ISOLATOR # BLOCK OP operand. R
general BOOLEAN ST ISOLATOR # BLOCK R
InRef1 ORG ISOLATOR # OPEN setting. R
setSrcRef ObjectReference SP ISOLATOR # OPEN reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG ISOLATOR # CLOSED setting. R
setSrcRef ObjectReference SP ISOLATOR # CLOSED reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3 ORG ISOLATOR # RESET setting R
setSrcRef ObjectReference SP ISOLATOR # RESET. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: ConInGGIO1 LDevice inst: System UR element: Contact Inputs
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Ind1Θ SPS Con Ip Θ On (φ) operand value R
stVal BOOLEAN ST Cont Ip φ On R
LNName: BkrΘXCBR# LDevice inst: System UR element: Breaker Control element #
data obj. data attribute Type FC UR Name Description R/W/C