3-156 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.4.6 Contact output interface (ConOut)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-177: Contact output data objects
3.5.4.7 Disconnect switch (Disc)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-178: Disconnect switch DiscCSWI data objects
Ind2Θ SPS Con Ip Θ Off (φ) operand value R
stVal BOOLEAN ST Cont Ip φ Off R
Ind2Θ SPS Instantiated only if the order code has
more than 99 contact inputs
R
stVal BOOLEAN ST Cont Ip φ Off R
Ind1Θ SPS Instantiated only if the order code has
more than 99 contact inputs
R
stVal BOOLEAN ST Cont Ip φ On R
LNName: ConOutGGIO1 LDevice inst: System UR element: Contact Outputs
data obj. data attribute Type FC UR Name Description R/W/C
Ind1Θ SPS only instantiated where the order code
indicates that contact output Θ is
equipped with a current detector
R
stVal BOOLEAN ST Cont Op φ IOn R
Ind2Θ SPS only instantiated where the order code
indicates that contact output Θ is
equipped with a voltage detector
R
stVal BOOLEAN ST Cont Op φ VOn R
Ind3Θ SPS only instantiated where the order code
indicates that contact output Θ is
equipped with a voltage detector
R
stVal BOOLEAN ST Cont Op φ VOff R
Ind4Θ SPS Con Op Θ On (φ) operand value R
stVal BOOLEAN ST Cont Op φ On R
InRef1Θ ORG CONTACT OUTPUT φ OPERATE setting. R
setSrcRef ObjectReference SP CONTACT OUTPUT φ OPERATE
setting
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2Θ ORG only instantiated where the order code
indicates that contact output Θ is not a
latching output.
R
setSrcRef ObjectReference SP CONTACT OUTPUT φ SEAL-IN
setting
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3Θ ORG only instantiated where the order code
indicates that contact output Θ
is a
latching output.
R
setSrcRef ObjectReference SP OUTPUT φ RESET setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DiscCSWI# LDevice inst: System UR element: Disconnect Control element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
LNName: ConInGGIO1 LDevice inst: System UR element: Contact Inputs
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents