3-162 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.4.8 Field contact inputs (FCIn)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-182: Field contact input data objects
3.5.4.9 Field contact outputs (FCOut)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
stVal BOOLEAN ST Disc0XSWI#.BlkOpn.stVal R
ctlModel CtlModels CF 0 R
BlkCls SPC Disconnect switch close commands
blocked from all sources
R
stVal BOOLEAN ST Disc0XSWI#.BlkCls.stVal R
ctlModel CtlModels CF 0 R
InRef1 ORG SWITCH # φA/3P CLSD setting” if Θ=”1”,
“SWITCH # φB CLSD setting” if Θ=”2”, or
“SWITCH # φC CLSD setting” if Θ=”3
R
GEORG R
setSrcRef ObjectReference SP SWITCH # φA/3P CLSD if Θ=”1”,
SWITCH # φB CLSD if Θ=”2”, or
SWITCH # φC CLSD if Θ=”3”
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
InRef2 ORG SWITCH # φA/3P OPND setting” if Θ=”1”,
“SWITCH # φB OPND setting” if Θ=”2”, or
“SWITCH # φC OPND setting” if Θ=”3
R
GEORG R
setSrcRef ObjectReference SP SWITCH # φA/3P OPND if Θ=”1”,
SWITCH # φB OPND if Θ=”2”, or
SWITCH # φC OPND if Θ=”3”
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: FCInGGIO1 LDevice inst: System UR element: Field Contact Inputs
data obj. data attribute Type FC UR Name Description R/W/C
IndΘ SPS FCI Θ On operand value R
stVal BOOLEAN ST FCI Θ On R
LNName: DiscΘXSWI# LDevice inst: System UR element: Disconnect Control element #
data obj. data attribute Type FC UR Name Description R/W/C