CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-175
3
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS A.phsB DEADBAND R/W/C
zeroDb INT32U CF current cut-off level. R
AcRMS MV SRC # Phase C Current RMS, in primary
amperes
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase C Current RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS A.phsC DEADBAND R/W/C
zeroDb INT32U CF current cut-off level. R
AresRMS MV SRC # Neutral Current RMS, in primary
amperes
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Neutral Current RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS A.neut DEADBAND R/W/C
zeroDb INT32U CF current cut-off level. R
Adif CMV SRC # Differential Ground Current phasor,
in primary amperes
R
instCVal Vector MX R
instCVal.mag.f FLOAT32 SRC # Differential Ground
Current Magnitude
R
instCVal.ang.f FLOAT32 SRC # Differential Ground
Current Angle
UR range -180...+180 converted to 0...360R
cVal Vector MX R
cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# Dif Gnd Cur.db R/W/C
dbAng INT32U CF MMXU# Dif Gnd Cur.dbAng R/W/C
zeroDb INT32U CF current cut-off level. R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
W WYE SRC # Phase Real Power, in primary wattsR
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 SRC # Phase A Real Power R
phsA.cVal Vector MX R
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C