3-174 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
phsB.units.SIUnit ENUMERATED 5, the code for primary amperes R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF MMXU# A.phsB.db R/W/C
phsB.dbAng INT32U CF MMXU# A.phsB.dbAng R/W/C
phsB.zeroDb INT32U CF current cut-off level. R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 SRC # Phase C Current
Magnitude
R
phsC.instCVal.ang
.f
FLOAT32 SRC # Phase C Current Angle UR range -180...+180 converted to 0...360R
phsC.cVal Vector MX R
phsC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsC.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsC.units Unit CF R
phsC.units.SIUnit ENUMERATED 5, the code for primary amperes R
phsC.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsC.db INT32U CF MMXU# A.phsC.db R/W/C
phsC.dbAng INT32U CF MMXU# A.phsC.dbAng R/W/C
phsC.zeroDb INT32U CF current cut-off level. R
res CMV R
res.instCVal Vector MX R
res.instCVal.mag
.f
FLOAT32 SRC # Neutral Current
Magnitude
R
res.instCVal.ang
.f
FLOAT32 SRC # Neutral Current Angle UR range -180...+180 converted to 0...360R
res.cVal Vector MX R
res.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
res.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
res.units Unit CF R
res.units.SIUnit ENUMERATED 5, the code for primary amperes R
res.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
res.db INT32U CF MMXU# A.neut.db R/W/C
res.dbAng INT32U CF MMXU# A.neut.dbAng R/W/C
res.zeroDb INT32U CF current cut-off level. R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
AaRMS MV SRC # Phase A Current RMS, in primary
amperes
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase A Current RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS A.phsA DEADBAND R/W/C
zeroDb INT32U CF current cut-off level. R
AbRMS MV SRC # Phase B Current RMS, in primary
amperes
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase B Current RMS R
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C