3-182 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.5.4  Demand metering (DmdMtr)
This element is instantiated in the following products: B30, C60, D60, F35, F60, G60, L60, L90, N60, T60.
Table 3-201: Demand metering data objects
units.SIUnit ENUMERATED 33, the code for hertz (1/s) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF B_FrqMMXN1.TrcHz.db R/W/C
zeroDb INT32U CF 0 R
LNName: DmdMtrMMTR# LDevice inst: Meter UR element: Signal Source  # NAME Demand Metering
data obj. data attribute Type FC UR Name Description R/W/C
ClcExp SPS Status information to indicate the 
calculation period has expired
R
stVal BOOLEAN ST TRUE | FALSE R
ClcMth ENG Calculation method of statistical data 
objects
R
setVal ENUMERATED SP UNSPECIFIED R
InSyn ORG Only instantiated in DmdMtrMMTR1 R
setSrcRef ObjectReference SP DEMAND TRIGGER reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
RsStat SPC Only instantiated in DmdMtrMMTR1.  
Clears demand for all sources.
R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
   .cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 0 indicates the duration is locally defined R
pulseConfig
   .offDur
INT32U 0 R
pulseConfig
   .numPls
INT32U 1 R
ctlModel CtlModels CF DmdMtrMMTR1.RsStat.ctlModel R/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
AaDmd MV SRC # DMD IA, in primary amperes R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # DMD IA R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF DmdMtrMMTR#.AaDmd.db R/W/C
zeroDb INT32U CF current cut-off level.  R
AaMaxDm
dDt
MV SRC # DMD IA MAX, in primary amperes 
with associated date, SRC # DMD IA DATE
R
mag AnalogueValue MX R
mag.f FLOAT32 SRC # DMD IA MAX R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for primary amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
AbDmd MV SRC # DMD IB, in primary amperes R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # DMD IB R
LNName: B_FrqMMXN1 LDevice inst: Meter UR element: B90 Metering for frequency
data obj. data attribute Type FC UR Name Description R/W/C