3-196 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6.12 Oscillography (Osc)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-215: Oscillograph data objects
stVal BOOLEAN ST LATCH # ON R
Ind2 SPS ”LATCH # OFF operand value R
stVal BOOLEAN ST LATCH # OFF R
InRef1 ORG Non-Volatile Latch LATCH # SET setting. R
setSrcRef ObjectReference SP Non-Volatile Latch SET setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG Non-Volatile Latch LATCH # RESET
setting.
R
setSrcRef ObjectReference SP Non-Volatile Latch RESET settingreference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: OscRDRE1 LDevice inst: Gen UR element: Oscillography, core logical node
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
RcdMade SPS Records are available R
stVal BOOLEAN ST R
FltNum INS NUMBER OF TRIGGERS actual value R
stVal INT32 ST NUMBER OF TRIGGERS actual
value
R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
NumRcd INS AVAILABLE RECORDS actual value R
stVal INT32 ST actual value AVAILABLE
RECORDS
R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
NumCycPe
r
INS CYCLES PER RECORD actual value R
stVal INT32 ST actual value CYCLES PER
RECORD
R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
RsTms INS LAST CLEARED DATE actual value R
stVal INT32 ST actual value LAST CLEARED DATE R
units Unit CF R
units.SIUnit ENUMERATED 4 R
units.multiplier ENUMERATED 0 R
RcdTrg SPC External command to trigger recorder R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 R
pulseConfig
.offDur
INT32U 0 R