CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-197
3
3.5.6.13 Real time clock (TmClk)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-216: Real-time clock data objects
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF OscRDRE1.RcdTrg.ctlModel R/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
MemClr SPC Clear all oscillography records command R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF OscRDRE1.MemClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
LNName: TmClkLTMS1 LDevice inst: Gen UR element: REAL TIME CLOCK feature except LOCAL TIME
data obj. data attribute Type FC UR Name Description R/W/C
TmAcc INS ACCURACY in number of significant bits in
the Fraction Of Second
R
stVal INT32 ST R
TmSrc VSS RTC Sync Source R
stVal VISIBLE
STRING255
SP Dotted decimal IP address of the
time source
R
TmChSt1 SPS Time channel status R
stVal BOOLEAN ST logical OR of SNTP, PTP or IRIG-B
time synchronization status.
R
TmSynSrc ENS RTC Sync Source actual value indicates
time synchronizing source the device is
using at present
R
stVal ENUMERATED ST Actual Value: RTC Sync Source. R
PTPChSt$ SPS PTP Port $ Status R
stVal BOOLEAN ST R
GrdMasterI
D
VSS GrandMaster ID actual value R
stVal VISIBLE STRING
255
ST GrandMaster ID R
TmnsDelta MV PTP-IRIG-B Delta in ns R
instMag AnalogueValue MX R
instMag.f FLOAT32 PTP-IRIG-B Delta R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED -9, the code for a multiplier of 10-9 R
db INT32 CF TmClkLTMS1.TmnsDelta.db R/W/C
zeroDb INT32 CF 0 R
LNName: OscRDRE1 LDevice inst: Gen UR element: Oscillography, core logical node