3-198 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6.14 Security (Sec)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-217: Security data objects
LNName: SecGSAL1 LDevice inst: Gen UR element: UR Basic Security element
data obj. data attribute Type FC UR Name Description R/W/C
AuthFail SEC Number of authorisation failures: an
association to the client could not be
established due to an authorisation
failure (fixed at 0)
R
cnt INT32U ST 0 R
sev ENUMERATED ST 2=major R
AcsCtlFail SEC Counter for Access control failures
detection (fixed at 0)
R
cnt INT32U ST 0 R
sev ENUMERATED ST 0=Unknown R
SvcViol SEC Counter for Service Violations R
cnt INT32U ST a new counter which increments
by 1, every time the data object
that the client wanted to access
exists, but the requested service
is not allowed
R
sev ENUMERATED ST 3 = Minor R
Ina SEC Counter for number of associations
terminated due to inactivity
R
cnt INT32U ST New counter that counts
number of associations
terminated due to inactivity
R
sev ENUMERATED ST 0=Unknown R
SecDataClr SPC Mapped to command Clear Security DataR/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 0 indicated the duration is locally definedR
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF a new setting
SecGSAL1.SecDataClr.ctlModel
default value 1, range 1…2
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
OpCntRs INC Data object to clear all 5 security violation
counters
R/Ctrl
stVal INT32 ST Sum of AuthFail + AcsCtlFail +
SvcViol + Ina
R
ctlModel CtlModels CF a new setting
SecGSAL1.OpCntRs ctlModel
default value 1, range 1…2
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
LocSetAcs
Off
SPS ACCESS LOC STG OFF operand R
stVal BOOLEAN ST ACCESS LOC STG OFF R
LocSetAcs
On
SPS ACCESS LOC STG ON operand R
stVal BOOLEAN ST ACCESS LOC STG ON R
LocCmdAc
sOn
SPS ACCESS LOC CMND ON operand R

Table of Contents