CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-199
3
3.5.6.15 Selector switch (SelSw)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-218: Selector switch data objects
stVal BOOLEAN ST ACCESS LOC CMND ON R
LocCmdAc
sOff
SPS ACCESS LOC CMND OFF operand R
stVal BOOLEAN ST ACCESS LOC CMND OFF R
RemSetAcs
On
SPS ACCESS REM STG ON operand R
stVal BOOLEAN ST ACCESS REM STG ON R
RemSetAcs
Off
SPS ACCESS REM STG OFF operand R
stVal BOOLEAN ST ACCESS REM STG OFF R
RemCmdA
csOn
SPS ACCESS REM CMND ON operand R
stVal BOOLEAN ST ACCESS REM CMND ON R
RemCmdA
csOff
SPS ACCESS REM CMND OFF operand R
stVal BOOLEAN ST ACCESS REM CMND OFF R
InRef1 ORG LOCAL SETTING AUTH setting. R
setSrcRef ObjectReference SP LOCAL SETTING AUTH setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG REMOTE SETTING AUTH setting. R
setSrcRef ObjectReference SP REMOTE SETTING AUTH setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: SelSwGAPC# LDevice inst: Gen UR element: Selector Switch element #
data obj. data attribute Type FC UR Name Description R/W/C
IndY SPS SELECTOR # POS Y operand value R
stVal BOOLEAN ST SELECTOR # POS Y R
Indα SPS SELECTOR # BIT β operand value R
stVal BOOLEAN ST SELECTOR # BIT β R
Alm2 SPS SELECTOR # STP ALARM operand value R
stVal BOOLEAN ST SELECTOR # STP ALARM R
Alm3 SPS ”SELECTOR # BIT ALARM operand value R
stVal BOOLEAN ST SELECTOR # BIT ALARM R
Alm1 SPS ”SELECTOR # ALARM operand value R
stVal BOOLEAN ST SELECTOR # ALARM R
Alm4 SPS ”SELECTOR # PWR ALARM operand value R
stVal BOOLEAN ST SELECTOR # PWR ALARM R
InRef1 ORG SELECTOR # STEP-UP setting. R
setSrcRef ObjectReference SP SELECTOR # STEP-UP setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG SELECTOR # ACK setting. R
setSrcRef ObjectReference SP SELECTOR # ACK setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3 ORG SELECTOR # 3BIT A0 setting. R
setSrcRef ObjectReference SP SELECTOR # 3BIT A0 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef4 ORG SELECTOR # 3BIT A1 setting. R
setSrcRef ObjectReference SP SELECTOR # 3BIT A1 setting reference to the data attribute to input R/C
LNName: SecGSAL1 LDevice inst: Gen UR element: UR Basic Security element