2-74 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Ground Time Overcurrent (Read/Write Grouped Setting) (1 or 6 Modules)
B30, C60, C70,
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, N60, T35,
T60
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
" 5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
" 5D03 Ground Time Overcurrent 1 Pickup 0.02 to 30 pu 0.001 F001 1000
" 5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod
Inv)
" 5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
" 5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0
(Instantaneo
us)
" 5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
B30, C60, C70,
D30, D60, F35,
F60, L30, L60,
L90, M60, N60,
T35, T60
5D11 ...Repeated for Ground Time Overcurrent 2
" 5D22 ...Repeated for Ground Time Overcurrent 3
" 5D33 ...Repeated for Ground Time Overcurrent 4
" 5D44 ...Repeated for Ground Time Overcurrent 5
" 5D55 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (1, 6, or 12 Modules)
B30, C60, C70,
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, N60, T35,
T60
5DA0 Ground Instantaneous Overcurrent 1
Function
0 to 1 --- 1 F102 0 (Disabled)
" 5DA1 Ground Instantaneous Overcurrent 1
Signal Source
0 to 5 --- 1 F167 0 (SRC 1)
" 5DA2 Ground Instantaneous Overcurrent 1
Pickup
0.02 to 30 pu 0.001 F001 1000
" 5DA3 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
" 5DA4 Ground Instantaneous Overcurrent 1 Reset
Delay
0 to 600 s 0.01 F001 0
" 5DA5 Ground Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 5DA7 Ground Instantaneous Overcurrent 1
Target
0 to 2 --- 1 F109 0 (Self-reset)
" 5DA8 Ground Instantaneous Overcurrent 1
Events
0 to 1 --- 1 F102 0 (Disabled)
" 5DA9 Reserved (8 items) 0 to 1 --- 1 F001 0
B30, C60, C70,
D30, D60, F35,
F60, L30, L60,
L90, M60, N60,
T35, T60
5DB1 ...Repeated for Ground Instantaneous
Overcurrent 2
" 5DC2 ...Repeated for Ground Instantaneous
Overcurrent 3
Products Address Register name Range Units Step Format Default

Table of Contents