CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-75
2
" 5DD3 ...Repeated for Ground Instantaneous
Overcurrent 4
" 5DE4 ...Repeated for Ground Instantaneous
Overcurrent 5
" 5DF5 ...Repeated for Ground Instantaneous
Overcurrent 6
C60, C70, D30,
D60, F35, F60,
L30, L60, L90,
M60, N60, T35,
T60
5E06 ...Repeated for Ground Instantaneous
Overcurrent 7
" 5E17 ...Repeated for Ground Instantaneous
Overcurrent 8
" 5E28 ...Repeated for Ground Instantaneous
Overcurrent 9
" 5E39 ...Repeated for Ground Instantaneous
Overcurrent 10
" 5E4A ...Repeated for Ground Instantaneous
Overcurrent 11
" 5E5B ...Repeated for Ground Instantaneous
Overcurrent 12
CT Fail (Read/Write Setting) (2, 4, or 6 Modules)
D30, D60, F60,
G30, G60, L30,
L60, L90, M60,
N60, T35, T60
5E6C CT Fail 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 5E6D CT Fail 1 Block 0 to 4294967295 --- 1 F300 0
" 5E6F CT Fail 1 Current Source 1 0 to 5 --- 1 F167 0 (SRC 1)
" 5E70 CT Fail 1 Current Pickup 1 0.1 to 2 pu 0.1 F001 2
" 5E71 CT Fail 1 Current Source 2 0 to 5 --- 1 F167 1 (SRC 2)
" 5E72 CT Fail 1 Current Pickup 2 0.1 to 2 pu 0.1 F001 2
" 5E73 CT Fail 1 Voltage Source 0 to 5 --- 1 F167 0 (SRC 1)
" 5E74 CT Fail 1 Voltage Pickup 0.04 to 2 pu 0.01 F001 20
" 5E75 CT Fail 1 Pickup Delay 0 to 65.535 s 0.001 F001 1000
" 5E76 CT Fail 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 5E77 CT Fail 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 5E78 ...Repeated for CT Fail 2
D60, F60, G30,
G60, L60, L90,
M60, N60, T35,
T60
5E84 ...Repeated for CT Fail 3
" 5E90 ...Repeated for CT Fail 4
N60, T35, T60 5E9C ...Repeated for CT Fail 5
" 5EA8 ...Repeated for CT Fail 6
Incipient Cable Fault Detector Actual Values (Read Only) (1, 2, or 6 Modules)
D30, F35, F60,
L30
5EC0 Incipient Cable Fault Detector 1 Phase A
Counter
0 to 65535 --- 1 F001 0
" 5EC1 Incipient Cable Fault Detector 1 Phase B
Counter
0 to 65535 --- 1 F001 0
" 5EC2 Incipient Cable Fault Detector 1 Phase C
Counter
0 to 65535 --- 1 F001 0
F35, F60 5EC3 ...Repeated for Incipient Cable Fault
Detector 2
Products Address Register name Range Units Step Format Default