GE Multilin D30 Line Distance Protection System 5-167
5 SETTINGS 5.6 GROUPED ELEMENTS
5
5.6.10 NEGATIVE SEQUENCE CURRENT
a) MAIN MENU
PATH: SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT
The D30 relay provides two (2) negative-sequence time overcurrent elements, two (2) negative-sequence instantaneous
overcurrent elements, and two (2) negative-sequence directional overcurrent elements. For additional information on the
negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier.
NEGATIVE SEQUENCE
CURRENT
NEG SEQ TOC1
See page 5–167.
MESSAGE
NEG SEQ TOC2
See page 5–167.
MESSAGE
NEG SEQ IOC1
See page 5–169.
MESSAGE
NEG SEQ IOC2
See page 5–169.
MESSAGE
NEG SEQ DIR OC1
See page 5–170.
MESSAGE
NEG SEQ DIR OC2
See page 5–170.