2-2 D30 Line Distance Protection System GE Multilin
2.1 INTRODUCTION 2 PRODUCT DESCRIPTION
2
Figure 2–1: SINGLE LINE DIAGRAM
2.1.2 ORDERING
a) OVERVIEW
The D30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod-
ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. See the GE Multilin ordering page at
http://www.gedigitalenergy.com/multilin/order.htm for the latest ordering options.
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu-
lar CT/VT modules or the HardFiber
TM
modules). The order code options are described in the following sub-sections.
Table 2–2: OTHER DEVICE FUNCTIONS
FUNCTION FUNCTION FUNCTION
Breaker arcing current (I
2
t) Fault detector and fault report Time synchronization over IRIG-B or
IEEE 1588
Breaker control Fault locator Time synchronization over SNTP
Broken conductor detection FlexElements™ (8) Transducer inputs and outputs
Contact inputs (up to 96) FlexLogic equations Trip bus
Contact outputs (up to 64) IEC 61850 communications (optional) User-definable displays
Control pushbuttons Line pickup User-programmable LEDs
CyberSentry™ security Metering: current, voltage, power, power
factor, frequency
User-programmable pushbuttons
Digital counters (8) Modbus communications User-programmable self-tests
Digital elements (48) Modbus user map Virtual inputs (64)
Direct inputs and outputs (32) Non-volatile latches Virtual outputs (96)
Disconnect switches (8) Non-volatile selector switch VT fuse failure
DNP 3.0 or IEC 60870-5-104 protocol Oscillography
Event recorder Setting groups (6)
837764A2.CDR
50N
(2)
51N
(2)
67N/G
(2)
21G
(5)
59P
27P
(2)
59N
52
79
50P
(2)
50_2
(2)
51
(2)
51_2
(2)
21P
(5)
67P
(2)
67_2
(2)
68
59X
78
27X
50G
(2)
51G
(2)
50DD
Monitoring
D30 Line Distance Protection System
Close Trip
25 (4)
Transducer
Inputs
Metering