DGP Digital Generator Protection System GE Power Management
2.1 GENERAL 2 CALCULATION OF SETTINGS
2
2503 DI3 ALRM 0000 to 1111 N/A 0000
2504
dg
DI3 TIMR
e
0.00 to 9.99 sec. 0.01
2505
(2504
g
)
DI4 TRIP 0000 to 1111 N/A 0000
2506
(2505
g
)
DI4 ALRM 0000 to 1111 N/A 0000
2507
de
DI4 TIMR 0.00 to 9.99 sec. 0.01
2508
e
DI6 FUNC EXTVTFF (0); DISPROT (1) N/A EXTVTFF
VOLTAGE TRANSFORMER FUSE FAILURE: VTFF
2601 VTFF DISABLE (0); ENABLE (1) N/A DISABLE
ACCIDENTAL ENERGIZATION: AE
2701 TRIP 0000 to 1111 N/A 0000
2702 ALARM 0000 to 1111 N/A 0000
2703 AE ARM AND (0); OR (1) N/A AND
GROUND OVERCURRENT: 51GN
2801
e
TRIP 0000 to 1111 N/A 0000
2802
e
ALARM 0000 to 1111 N/A 0000
2803
e
PICKUP 0.10 to 5.00 0.02 to 1.00 A 0.50 0.10
2804
e
TIME FAC 0.10 to 99.99 sec. 1.00
UNDERVOLTAGE: 27
2901
e
TRIP 0000 to 1111 N/A 0000
2902
e
ALARM 0000 to 1111 N/A 0000
2903
e
PICKUP 40 to 210
d
V100
2903
e
PICKUP 40 to 120
f
V100
2904
e
TIME FAC 0.1 to 99.99 sec. 1.00
2905
e
CURVE # 1 (Inverse); 2 (Definite Time) N/A 1
UNDERVOLTAGE – THIRD HARMONIC: 27TN
3001
de
TRIP 0000 to 1111 N/A 0000
3002
de
ALARM 0000 to 1111 N/A 0000
Table 2–1: DGP SYSTEM SETTINGS & RATINGS (Sheet 6 of 7)
SETTING
NUMBER
MNEMONIC RANGE DEFAULT
5 AMP 1 AMP UNITS 5 AMP 1 AMP
c