c) placing the temperature sensor in the cold well.
d) Measure the temperature and start cutting in this position.
- The card must be cut and start the compressor relay after the temperatures of the table.
Temp
Temp
1
7.02 1.39
2
7.02 1.39
4
1.69 -1.67
5
1.69 -1.67
6
1.69 -1.67
7
8
0.44 -2.33
9
-0.28 -3.06
e) Remove the power supply to the card.
Note: In position 0 must remain off the compressor and defrost relays
Check defrost relay (CTQ).
a) Feeding 127VAC control card in the main connector.
b) Wait for the compressor relay is activated.
c) Force the melting by a short circuit between pins VCC and P1
d) The compressor will stop relay and defrost relay will be activated.
e) Remove the power supply to the card.