14 Kilsen KFP-CF Series Operation Manual
Enabling or disabling a configured extended fire routing delay
If configured, the extended fire routing delay is enabled or disabled at the same time
as the standard fire routing delay.
In NEN 2535 operating mode, the extended fire routing delay becomes the active
delay when sounders are stopped (by pressing the Sounder Start/Stop button) and
remain stopped when the standard fire routing delay time has elapsed.
In EN 54-2 Scandinavia operating mode, the extended fire routing delay becomes the
active delay when an extended fire routing delay switch is activated while the
standard fire routing delay elapses.
Testing a zone
To test a zone, press the general Test button, and then press the corresponding Zone
button. The maximum number of zones that may be tested at the same time is four.
A zone in test is indicated as follows:
The general Test LED is steady.
The Zone Fault/Disable/Test LED is steady.
When an alarm is activated in a zone in test:
The general Fire Alarm LEDs and Zone alarm LED are steady or flashing,
depending on the source of the alarm.
Fire routing and other zone-dependent functions are not activated.
Unless configured otherwise, the sounders are activated for five seconds and the
Sounder Start/Stop LED is steady (see note).
Unless configured otherwise, the internal buzzer sounds constantly (see note).
The control panel will reset automatically after five seconds and clear alarms for
the zone in test.
To end the test, press the Test button, and then press the Zone button again.
If there is a fire alarm in another zone not in test, the control panel responds to the
alarm event as configured.
Note: The internal buzzer and sounders may be configured not to sound when an
alarm is activated in a zone being tested. Contact your fire system installation or
maintenance contractor to confirm your configuration details.
Disabling a zone or enabling a disabled zone
To disable a zone, press the general Disable button, and then press the
corresponding Zone button.
A disabled zone is indicated as follows:
The general Disable LED is steady.
The zone Fault/Disable/Test LED is steady.
To enable the zone, press the general Disable button, and then press the Zone button
again.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Kilsen KFP-CF Series and is the answer not in the manual?

GE Kilsen KFP-CF Series Specifications

General IconGeneral
BrandGE
ModelKilsen KFP-CF Series
CategoryControl Panel
LanguageEnglish

Related product manuals