EasyManua.ls Logo

GE MDP

GE MDP
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK
-
100682
The
use
of
a
separate
grounid
-
overcurrent
function
is
advantageous
because
it
can
generally
be
adjusted
to
provide
faster
and
more
sensitive
protection
for
single
-
phase
-
to
-
ground
faults
'
than
the
phase
-
overcurrent
functions
.
Typical
connections
for
such
an
application
are
shown
in
Figures
9
and
10
,
This
safety
factor
can
be
reduced
to
0.07
second
if
the
time
unit
is
instead
set
to
the
desired
time
accurate
tests
.
by
#
The
instantaneous
-
overcurrent
unit
can
be
applied
in
many
instances
to
reduce
the
fault
-
clearing
time
for
high
-
fault
currents
.
This
unit
is
normally
set
to
pick
up
only
on
internal
faults
in
the
protected
zone
.
Significant
transient
overreach
can
be
experienced
under
certain
conditions
,
and
this
must
be
taken
into
account
by
selecting
a
pickup
setting
that
is
higher
than
that
which
would
be
dictated
by
the
maximum
steady
-
state
external
-
fault
current
.
The
pickup
setting
of
the
MDP
time
unit
should
be
chosen
so
that
it
will
operate
for
all
short
circuits
in
the
protected
zone
,
and
also
provide
back
-
up
protection
for
short
circuits
in
the
immediately
-
adjacent
system
element
when
possible
.
The
time
-
unit
pickup
should
be
set
low
enough
to
ensure
that
the
minimum
fault
current
is
at
least
1.5
times
the
setting
.
IMPORTANT
NOTE
If
one
unit
(
instantaneous
or
inverse
)
operates
,
the
other
unit
(
inverse
or
instantaneous
)
will
also
operate
.
The
MDP
s
fault
report
will
record
the
first
fault
that
occurred
.
When
the
fault
is
cleared
the
MDP
s
fault
LED
s
will
display
Phase
-
Phase
,
Phase
-
Ground
,
Instantaneous
and
inverse
time
faults
.
See
display
section
on
how
to
interpret
the
display
for
various
fault
conditions
.
The
MDP
will
generate
a
new
fault
report
when
the
fault
current
drops
below
the
pick
-
up
value
and
a
new
fault
occurs
.
The
time
-
delay
adjustment
of
the
time
unit
should
be
chosen
to
assure
selectivity
with
the
protection
on
the
adjacent
system
elements
.
This
adjustment
should
be
made
for
the
condition
that
yields
maximum
fault
current
at
the
relay
location
.
The
time
delay
is
determined
by
the
adjacent
relay
operating
time
for
this
condition
,
plus
a
coordinating
time
allowance
that
includes
the
adjacent
circuit
-
breaker
maximum
operating
time
and
a
safety
factor
to
accommodate
any
uncertainties
.
Since
the
MDP
time
unit
has
insignificant
overtravel
,
the
only
relay
variation
that
needs
consideration
in
the
safety
factor
is
the
tolerance
on
the
time
curves
.
A
0.17
-
second
safety
factor
is
generally
used
if
the
relay
time
is
determined
by
selecting
a
time
-
dial
setting
from
the
time
curves
.
i
Contact
converter
input
CC
1
and
the
output
-
select
switch
of
the
MDP
allow
a
Zone
Selective
Interlocking
of
the
MDP
relays
.
This
scheme
provides
instantaneous
operation
(
with
a
minimum
time
delay
)
of
the
upstream
relay
for
faults
between
the
upstream
and
downstream
relays
.
Refer
to
Figure
11
for
a
typical
scheme
and
settings
considerations
.
Note
that
all
the
feeders
must
be
radial
,
with
no
,
or
very
weak
,
source
.
TECHNICAL
SPECIFICATIONS
Nominal
frequency
:
25
/
50
/
60
Hz
t
!
Nominal
current
:
1
or
5
amps
24
-
48
VDC
(
19
to
60
VDC
)
48
-
125
VDC
/
AC
(
38.5
to
150
VDC
/
AC
)
35
to
120
AC
110
-
250
VDC
(
88
to
285
VDC
)
85
to
240
AC
0.1
-
0.875
/
0.3
-
2.65
=
0.09
/
,
2.8
°
at
60
Hz
(
2.25
VA
at
5
A
)
0.1
-
0.875
/
0.3
-
2.65
=
0.09
/
,
2.4
°
at
50
Hz
(
2.25
VA
at
5
A
)
0.5
-
4.375
/
1.5
-
13.25
=
0.01
/
,
11.5
°
at
60
Hz
(
0.25
VA
at
5
A
)
0.5
-
4.375
/
1.5
-
13.25
=
0.01
/
,
9
,
7
°
at
50
Hz
(
0.25
VA
at
5
A
)
Less
than
3
watts
at
all
voltages
,
quiescent
Less
than
4.5
watts
at
maximum
voltages
Auxiliary
power
supply
:
AC
Burden
:
DC
6
Courtesy of NationalSwitchgear.com

Other manuals for GE MDP

Related product manuals