GEK
-
100682
-
20
°
to
+
65
°
C
(
-
40
°
C
available
upon
request
)
-
40
°
to
+
65
°
C
Operating
:
Storage
:
Temperature
:
Overcurrent
Ratings
:
2
x
In
Three
Second
;
50
x
In
One
Second
:
100
x
In
Continuous
:
RATINGS
I
/
t
CT
34500
87500
13600
1
AMP
5
AMP
*
1
AMP
SPECIAL
*
Models
MDPx
6
have
a
sensitive
ground
CT
.
Relative
Humidity
:
Up
to
95
%
without
condensing
<
:
Accuracy
:
Operating
Value
:
Operating
Time
:
5
%
5
%
or
0.025
seconds
,
whichever
is
greater
Repeatability
:
Operating
Value
:
Operating
Time
:
1
%
2
%
or
0.025
seconds
,
whichever
is
greater
Output
and
Trip
Contacts
:
Closing
:
1
Contact
will
close
and
conduct
up
to
a
maximum
of
30
amps
for
tripping
duty
at
control
voltages
up
to
300
VDC
.
The
output
contact
is
also
rated
for
Capacitive
trip
devices
.
Interrupting
:
50
watts
resistive
with
a
maximum
of
2
amps
and
300
VDC
Continuous
:
5
amps
,
with
300
VDC
maximum
25
-
70
Hz
(
Note
:
responds
to
RMS
values
of
harmonics
to
600
Hz
)
Frequency
operating
range
:
Communications
Address
:
002
to
998
r
.
'
T
-
rv
§
NOTE
Interference
suppression
ground
connection
This
connection
should
be
as
short
as
possible
,
to
assure
maximum
protection
,
conductors
are
recommended
.
The
MDP
relay
contains
high
-
frequency
interference
protection
consisting
of
a
series
of
capacitors
connected
between
the
input
terminals
and
the
case
,
Braided
#
12
AWG
The
case
stud
of
the
relay
should
be
connected
to
ground
,
so
these
interference
suppression
circuits
can
perform
their
protective
function
.
7