SECTION
3
DISASSEMBLING
THE
BREAKER
LOAD
TERMINAL
BRACKET
SCREWS
Removal
of
the
Old
Trip
Units
METAL
BREAKER
FRAMES
Step
1
.
Remove
and
discard
the
(
2
)
load
terminal
bracket
screws
from
the
back
of
each
trip
unit
housing
.
(
Fig
14
)
Step
2
.
Remove
and
discard
the
(
2
or
4
)
trip
unit
screws
from
the
back
of
each
trip
unit
housing
.
(
Fig
.
14
)
Step
3
.
Remove
and
discard
the
(
2
)
load
terminal
screws
on
the
top
of
each
trip
unit
(
Fig
.
15
)
.
Discard
the
electromechanical
trip
units
.
Step
4
.
Separate
the
load
terminal
bracket
from
the
old
load
terminal
(
Fig
.
16
)
.
Discard
the
load
termi
-
nal
and
the
hardware
,
but
save
the
bracket
.
TRIP
UNIT
SCREWS
Fig
.
14
.
Trip
Unit
Disassembly
(
Back
)
1
,
TOP
BUS
SCREWS
rrm
Fig
.
15
.
Trip
Unit
Disassembly
(
Top
)
LOAD
TERMINAL
BRACKET
Fig
.
16
.
Load
Terminal
and
Bracket
9
Courtesy of NationalSwitchgear.com

Other manuals for GE MicroVersaTrip PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MicroVersaTrip PM and is the answer not in the manual?

GE MicroVersaTrip PM Specifications

General IconGeneral
BrandGE
ModelMicroVersaTrip PM
CategoryCircuit breakers
LanguageEnglish

Related product manuals